Plan Review Notes
Plan Review Notes For Permit 16071135
Permit Number 16071135
Review Stop E
Sequence Number 1
Notes
Date Text
2016-08-01 12:26:12JOB PERMIT NUMBER: 16071135
 JOB ADDRESS: 1897 PALM BEACH LAKES BLVD
 WEST PALM BEACH FLORIDA
 DATE: AUGUST 1, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1) CURRENT AND APPLICABLE CODES IN EFFECT ARE NFPA 72
 2010, NFPA 101 2012, AND NFPA 70 ( NEC ) 2011.
 2) LOW VOLTAGE SHALL BE UNDER A SEPARATE PERMIT.
 3) FBC-E C405.7.3 VOLTAGE DROP. FEEDERS & CUSTOMER
 OWNED SERVICE CONDUCTORS SHALL BE SIZED FOR A MAXIMUM
 OF 2% VOLTAGE DROP. BRANCH CIRCUITS SHALL BE SIZED FOR
 A MAXIMUM OF 3% VOLTAGE DROP.
 4) ADD SERVICE RECEPTACLE OUTLET FOR MECHANICAL
 EQUIPMENT WITHIN 25' PER NEC 210.63 AND IF INSTALLED
 OUTDOORS THE DEVICE SHALL BE "WR", AND THE ENCLOSURE
 "WP" PER NEC 406.9(B).
 5) NEC 300.3(C)(1) CONDUCTOR INSULATION RATING WITHIN
 ENCLOSURES AND CABLES OR RACEWAYS SHALL BE OF EQUAL
 VOLTAGE, SEPARATION BARRIERS IN COMPLIANCE WITH NEC 725
 IS ACCEPTABLE. PLEASE CLARIFY FOR CONFERENCE ROOM FLOOR
 BOXES.
 6) IF BREAK ROOM AREA CONTAIN SINKS IN THE COUNTERTOP
 GFCI PROTECTION IS REQUIRED. NEC 210.8(B)(5)(6).
 7) PROVIDE A LUMINAIRE SUPPORT DETAIL THAT COMPLIES
 WITH NEC 410.36(B) MECHANICAL MEANS OF FASTENING OF
 LUMINAIRES TO SUSPENDED CEILINGS FRAMING MEMBERS.
 CEILING GRID ATTACHMENTS SHALL ALSO BE IN ACCORDANCE TO
 ANSI STANDARDS.
 8) SHOW AVAILABLE FAULT CURRENT FIELD MARKINGS ON
 SERVICE EQUIPMENT SINCE MODIFICATIONS ARE BEING MADE TO
 THE ELECTRICAL SYSTEM. NEC 110.24(A)(B). LABEL ALL
 PANELBOARDS WITH THEIR SOURCE OF SUPPLY ORIGINATION.
 NEC 408.4(B)
 9) CLARIFY ONE LINE-DIAGRAM RACEWAY SCHEDULE TO VERIFY
 WHY SOME CONDUITS DON'T HAVE AN EQUIPMENT GROUNDING
 CONDUCTOR? CLARIFY IF INTERCEPTING POINT FOR PANELS
 "A1" & "A2" IS A HANDHOLD OR A WIRE-WAY GUTTER? PROPER
 BONDING REQUIRED PER NEC 250. HOW WILL THE SERVICE TAP
 FROM EXISTING EQUIPMENT BE MADE, IS IT THROUGH DUAL LUG
 AND IF SO THE TAP BOX MUST BE IDENTIFIED PER NEC
 110.14.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME.
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE
 SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  