| Plan Review Notes For Permit 16071129 |
| Permit Number |
16071129 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-27 16:28:00 | CONDITIONAL ELECTRICAL APPROVAL CONTINGENT ON THE NOTES | | | MADE ON APPROVED PLANS: | | | 1. THE SERVICE OUTLET REQUIRED BY NEC 210.63 IS MISSING | | | AND SHALL BE INCLUDED. | | | 2. CORRECT OCPD FROM 20 AMP TO 25 PER MANUFACTURER'S | | | SPECS. |
|