| Plan Review Notes For Permit 16071123 |
| Permit Number |
16071123 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-30 03:02:20 | 1) SPECIFY WHAT THE AREA WITH THE LIGHT THAT IS | | | ADJACENT TO THE SPA IS PROPOSED TO BE. WPB AMEND. TO | | | FBC SEC. 107.2.1. | | | 2) THE NOTES ON SHEET 2 OF 2 AT THE POOL & SPA PIPE | | | SCHEMATIC ARE BECOMING DIFFICULT TO READ. PLEASE | | | ADDRESS THIS COMMENT FOR FUTURE SUBMITTALS AND ENSURE | | | THE NOTES ARE LEGIBLE. | | | 3) A BACKFLOW PREVENTION DEVICE WILL BE REQUIRED ON THE | | | WATER SERVICE. THIS SHALL BE DONE AS A SEPARATE PERMIT | | | SUBMITTAL. | | | 4) A TEST REPORT FROM AN INDEPENDENT LABORATORY IS | | | REQUIRED TO VERIFY PROCEDURE COMPLIANCE OF THE HEAT | | | PUMP WITH AHRI 1160 PER THE 2014 FBC-ENERGY | | | SEC.R403.9.1.2. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|