| 2016-07-29 18:07:37 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SPECIFY WHAT THE AREA BESIDE THE SPA WITH THE LIGHT | | | IS PROPOSED TO BE. FBC 107.2.1 | | | | | | 2) PROVIDE THE DIMENSIONS OF THE SPA AND THE AREA NEXT | | | TO IT THAT IS NOT IDENTIFIED ON THE PLANS. FBC 107.2.1 | | | | | | 3) SPECIFY HOW THE POOL WILL COMPLY WITH THE | | | RESIDENTIAL POOL BARRIER REQUIREMENTS. FBCR 4501.17 | | | | | | 4) SPECIFY HOW THE POOL EQUIPMENT WILL BE ANCHORED TO | | | RESIST WIND LOADS. FBCR 301.1 |
|