| Date |
Text |
| 2016-08-04 15:40:42 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THE SUBMITTED PLAN SHEETS ARE NOT BOUND OR |
| | ORGANIZED. |
| | |
| | 1.7.11 PLANS AND SPECIFICATIONS. |
| | 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | EACH SET OF PLAN SHEETS SHALL BE BOUND AND ORGANIZED TO |
| | AVOID CONFUSION AND/OR LOST SHEETS. |
| | |
| | |
| | 2) THERE IS NO REFERNCE TO ANY INDICATED NFPA CODE |
| | COMPLIANCE. |
| | |
| | 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | PLEASE PROVIDE THE APPLICABLE NFPA CODE. |
| | |
| | |
| | |
| | 3) THE SUBMITTED PALNS DO NOT INDICATE A SYMBOL/PRODUC |
| | TABLE. |
| | |
| | 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | |
| | PLEASE PROVICE THE APPLICABLE TABLE AND PRODUCT |
| | IDENTIFICATION. |
| | |
| | |
| | |
| | 4) A WIRING DIAGRAM OR WIRE DETAIL IS NOT INDICATED. |
| | |
| | 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | PLEASE PROVIDE ALL APPLICABLE WIRING INFORMATION |
| | INCLUDING THE FA SYSTEM SCHEMATIC DRAWING. |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |