Plan Review Notes
Plan Review Notes For Permit 16071104
Permit Number 16071104
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-08-04 15:40:42THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE SUBMITTED PLAN SHEETS ARE NOT BOUND OR
 ORGANIZED.
  
 1.7.11 PLANS AND SPECIFICATIONS.
 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 EACH SET OF PLAN SHEETS SHALL BE BOUND AND ORGANIZED TO
 AVOID CONFUSION AND/OR LOST SHEETS.
  
  
 2) THERE IS NO REFERNCE TO ANY INDICATED NFPA CODE
 COMPLIANCE.
  
 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 PLEASE PROVIDE THE APPLICABLE NFPA CODE.
  
  
  
 3) THE SUBMITTED PALNS DO NOT INDICATE A SYMBOL/PRODUC
 TABLE.
  
 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
  
 PLEASE PROVICE THE APPLICABLE TABLE AND PRODUCT
 IDENTIFICATION.
  
  
  
 4) A WIRING DIAGRAM OR WIRE DETAIL IS NOT INDICATED.
  
 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 PLEASE PROVIDE ALL APPLICABLE WIRING INFORMATION
 INCLUDING THE FA SYSTEM SCHEMATIC DRAWING.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  