| Plan Review Notes For Permit 16071099 |
| Permit Number |
16071099 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-10-22 06:36:51 | 1) SHT. A.2 - THE ROOM FINISH SCHEDULE IDENTIFIES THE | | | WALL FINISH IN THE MEN'S & WOMEN'S RESTROOMS AND | | | JANITOR'S ROOM AS "PAINT." COMPLY WITH 2014 FBC | | | SEC.1210.2.1. 1210.2.2. | | | 2) SHT. A.2 REFERS TO PERMIT #12070659 FOR THE | | | INSTALLATION OF THE ROUGH-IN PLUMBING AND SHT. A.1 | | | REFERS TO PERMIT #12070649. PERMIT #12070649 IS THE | | | CORRECT MASTER NUMBER. PERMIT NUMBER 12070659 APPLIES | | | TO 211 DYER ROAD AND IS OBVIOUSLY THE WRONG PERMIT | | | NUMBER. THE PLUMBING PEMIT NUMBER IS #13080552 AND | | | LIMITED PLUMBING INSPECTIONS WERE DONE UNDER THIS | | | PERMIT NUMBER AND THIS PLUMBING PERRMIT HAS NEVER | | | RECEIVED A FINAL PLUMBING INSPECTION. THE PERMIT SHALL | | | BE RENEWED AND ALL REMAINING REQUIRED INSPECTIONS SHALL | | | BE SCHEDULED AND COMPLETED. WPB AMENDMENTS TO FBC | | | SEC.105.4.1.2. REVISE THE NOTES ON SHTS. A.1 & A.2. | | | 3) CLARIFY WHAT OPERATIONS/PROCESSES OCCUR IN THE | | | "SUPPORT SPACE" SHOWN ON THE PLANS. | | | 4) SUPPLY A NARRATIVE RESPONSE TO THE PLUMBING COMENTS. | | | ONE HAS NOT BEEN PROVIDED FOR THE PREVIOUS PLUMBING | | | REVIEWS. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|