| Plan Review Notes For Permit 16071099 |
| Permit Number |
16071099 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-10-12 17:10:52 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #16071099 | | | 10/12/16 | | | | | | 1) REFER TO SECTION 306.5 AND PROVIDE AN INTERIOR OR | | | EXTERIOR ACCESS TO THE RTU'S THAT DOES NOT INVOLVE THE | | | USE OF PORTABLE LADDERS. THE NOTES ON SHEET A.3 | | | INDICATE NON-COMPLIANCE: A) THERE IS NO WAY TO ACCESS | | | THE ATTIC HATCH IN B-1 WITHOUT A PORTABLE LADDER. B) | | | THE MEANS OF ACCESS VIA THE ADJOINING TENANT OCCUPANCY | | | IS RESTRICTIVE BECAUSE THE BUSINESS MAY NOT BE OPEN | | | WHEN ACCESS IS NEEDED. | | | | | | 2) THE NEW CONDITIONED WAREHOUSE IS LABELED "EXHIBIT | | | HALL" ON SHEET M1.1, BUT ON ALL THE ARCHITECTURAL | | | SHEETS EXCEPT A1, IT IS LABELED "BANQUET HALL". AS | | | PREVIOUSLY NOTED IN THE PREVIOUS REVIEW, THE | | | VENTILATION RATE MUST BE INCREASED IF DINING HALL IS TO | | | BE THE USE OF THE SPACE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|