| Date |
Text |
| 2016-10-21 10:06:09 | 501 FERN STREET #101 |
| | PERMIT #16071099 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | PROVIDE A TITLE ON EACH SHEET FOR THE SIX OWNER |
| | DESIGNED SEATING LAYOUTS. EXAMPLE: SEATING OPTION 1, |
| | SEATION OPTION 2, ETC. OR SIMILAR. |
| | |
| | THE ROWS OF CHAIRS WILL NEED TO BE FASTENED TOGETHER |
| | FOR THE LAST SEATING PLAN (20 CHAIRS PER ROW; 15 ROWS): |
| | PER NFPA 101 SECTION 12.7.9.1.1 SEATS IN ASSEMBLY |
| | OCCUPANCIES ACCOMMODATING MORE THAN 200 PERSONS SHALL |
| | BE SECURELY FASTENED TO THE FLOOR, EXCEPT WHERE |
| | FASTENED TOGETHER IN GROUPS OF NOT LESS THAN THREE. |
| | |
| | DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE |
| | FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS HAVE |
| | BEEN SATISFIED. |
| | |
| | NOTE: SEPARATE PERMITS ARE REQUIRED FOR THE FIRE ALARM |
| | AND FIRE SPRINKLER DESIGN CHANGES NEEDED TO PROTECT THE |
| | SPACE. |
| | |
| | NOTE: FOR EACH EVENT, A SPECIAL EVENT PERMIT WILL BE |
| | NEEDED SHOWING THE EVENT TYPE, EVENT DATES, FURNITURE |
| | LAYOUT, # OF OCCUPANTS, INTERIOR FINISH MATERIALS, |
| | CROWD MANAGERS, ETC. A PLAN REVIEW AND FIRE INSPECTION |
| | WILL BE PERFORMED AT ADDITIONAL CHARGES FOR EACH EVENT |
| | ENSURING THE SAFETY OF THE EVENTS. PER NFPA 101 SECTION |
| | 12.7.6.1 ASSEMBLY OCCUPANCIES SHALL BE PROVIDED WITH A |
| | MINIMUM OF ONE TRAINED CROWD MANAGER OR CROWD MANAGER |
| | SUPERVISOR. WHERE THE OCCUPANT LOAD EXCEEDS 250, |
| | ADDITIONAL TRAINED CROWD MANAGERS OR CROWD MANAGER |
| | SUPERVISORS SHALL BE PROVIDED AT A RATIO OF ONE CROWD |
| | MANAGER OR CROWD MANAGER SUPERVISOR FOR EVERY 250 |
| | OCCUPANTS. THE CROWD MANAGER SHALL RECEIVE APPROVED |
| | TRAINING IN CROWD MANAGEMENT TECHNIQUES. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | |