Plan Review Notes
Plan Review Notes For Permit 16071099
Permit Number 16071099
Review Stop E
Sequence Number 3
Notes
Date Text
2016-10-20 21:48:022ND ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: 501 FERN STREET 101
 JOB ADDRESS: 501 FERN STREET
 DESCRIPTION: GENERAL BUILDING ALTERATIONS TO EXISTING
 BLDG.
 MASTER PERMIT: 16071099
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. PLEASE NOTE THAT PERMIT #13080450 IS NOW EXPIRED AND
 WITHOUT A FINAL ELECTRICAL INSPECTION. THEREFORE ALL OF
 THE ELECTRICAL WORK SHOWN ON THE DRAWINGS SHALL BE
 CONSIDERED NEW AND SHALL COMPLY WITH THE 2011 EDITION
 OF THE NEC. YOU SHALL REMOVE ALL REFERENCE TO ANY
 EXISTING WORK FROM THE DRAWINGS. FURTHERMORE, PERMIT
 13080450 WAS OBTAINED FOR TENANT AREA C AND NOT TENANT
 A.
 2. ACCORDING TO OUR RECORDS THERE HAVE ONLY BEEN
 SLAB/UNDERGROUND INSPECTIONS ON PERMIT 13080450 AND
 NEVER A FINAL THEREFORE THIS WORK IS CONSIDERED
 NONEXISTENT.
 3. REGARDLESS OF HAVING HAD PRIOR INSPECTIONS OR NOT,
 THE WIRING METHODS REQUIRED FOR THIS TYPE OF OCCUPANCY
 DIFFER GREATLY TO THOSE OF A WAREHOUSE OR STORAGE
 FACILITY OR EVEN AN EMPTY SHELL. BECAUSE THESE PREMISES
 WERE NOT DESIGNED AS ASSEMBLY AT THAT TIME, THOSE
 METHODS WERE NOT LOOKED FOR IN PLAN REVIEW.
  
 UNTIL WE ESTABLISH THE ABOVE, WE CAN?T PROCEED WITH
 THIS REVIEW, I WILL CONTINUE AND RESPONSE TO THE
 REMAINDER OF THE COMMENTS.
  
 4. NEC 518.4: A NOTE WILL BE PLACED ON THE RESUBMITTAL
 REMINDING THE INSPECTORS TO LOOK FOR ANY PVC CONDUIT
 WITHIN THE PREMISES.
 5. NEC 215.5: PROVIDE A SITE SPECIFIC ELECTRICAL RISER
 DIAGRAM INDICATING THE TYPE OF RACEWAYS BEING USED FOR
 THE FEEDERS OF THE TWO ELECTRIC PANELS DESCRIBED. PER
 NEC 518.4, PVC IS PROHIBITED IN ANY ASSEMBLY OCCUPANCY
 UNLESS ENCASED IN 2? OF CONCRETE. YOU SHALL PROVIDE AS
 PART OF THIS RISER SITE SPECIFIC LOAD CALCS TO INCLUDE
 THE LOAD FOR THE 4 INSTANT WATER HEATERS. REVISE YOUR
 CALCS AS SHOWN THE DEMAND LOAD FROM YOUR PANEL SCHEDULE
 IS GREATER THAN MENTIONED AND THEREFORE THE FEEDER AND
 OCP FOR THE PANEL WILL NEED TO BE A 400 AMP BREAKER.
 6. NEC 408.4(A): PROVIDE A CIRCUIT DIRECTORY FOR EACH
 OF THE TWO PANELS. ACCORDING TO THE SUBMITTED DIRECTORY
 THERE IS A SINGLE CIRCUIT FOR THE AREA LIGHTING. THOUGH
 THE PLANS SHOW TWO PANELS AND YOU CLAIM TO ONLY HAVE
 ONE. THAT WOULD BE IRRELEVANT AS ALL WORK WILL BE
 CONSIDERED NEW. FROM OUR PERSPECTIVE YOU CAN?T RELOCATE
 WHAT IS NOT THERE.
 7. NEC 210.62: AT LEAST ONE RECEPTACLE OUTLET SHALL BE
 INSTALLED WITHIN 18? OF THE TOP OF A SHOW WINDOW FOR
 EVERY 12 LINEAR FT. OR MAJOR PORTION THEREOF AREA
 MEASURED HORIZONTALLY. IN YOUR RESPONSE YOU SAY THAT
 THE WINDOW IS NOT A SHOW WINDOW. THE OCCUPANCY ITSELF
 IS AN EXHIBIT HALL AND THIS IS NOT A SHOW WINDOW? SHOW
 WINDOW OUTLETS SHALL BE INSTALLED AND ADDED TO THE LOAD
 CALCS AS PER NEC 220.14(G).
 8. NEC 210.63: HVAC EQUIPMENT SERVICE OUTLETS. A 125
 VOLT, SINGLE?PHASE, 15 OR 20?AMPERE?RATED RECEPTACLE
 OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR
 THE SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL
 BE LOCATED WITHIN 25 FT. OF THE EQUIPMENT. THIS
 INCLUDES THE RTU UNITS ON THE ROOF. I SEE YOU CORRECTED
 THIS ON THE PLANS.
 9. NEC 422.52: ELECTRIC DRINKING FOUNTAINS. ELECTRIC
 DRINKING FOUNTAINS SHALL BE PROTECTED WITH GROUND?FAULT
 CIRCUIT INTERRUPTER PROTECTION (GFI). I SEE YOU
 CORRECTED THIS ON THE PLANS.
 10. NEC 600.5: EACH COMMERCIAL BUILDING AND EACH
 COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS SHALL BE
 PROVIDED WITH AT LEAST ONE 20 AMP DEDICATED OUTLET IN
 AN ACCESSIBLE LOCATION AT EACH ENTRANCE TO EACH TENANT
 SPACE FOR SIGN OR OUTLINE LIGHTING. SERVICE HALLWAYS OR
 CORRIDORS SHALL NOT BE CONSIDERED ACCESSIBLE TO
 PEDESTRIANS. NONE OF THE THREE DOORS COMPLY. THIS
 INCLUDES ALL FOUR DOORS TO THE OUTSIDE. THE ONE OUTLET
 PLACED ON THE PLANS IS NOT WHAT IS REQUIRED. YOU SHALL
 INSTALL A DEDICATED SIGN OUTLET AT EVERY DOOR. THIS HAS
 TO BE CLOSE TO THE DOOR.
 11. NEC 700.12 (F) (4) ? EMERGENCY LIGHTING SHALL BE
 FED BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR
 MORE LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY
 BE ON OWN CIRCUIT. AS CLEARLY STATED HEREIN, YOU MUST
 HAVE A MINIMUM OF THREE LIGHTING CIRCUITS FOR THE ONE
 AREA BEFORE YOU CAN USE A DEDICATED EMERGENCY LIGHTING
 CIRCUIT, OTHERWISE THEY SHALL BE CONNECTED TO THE
 LIGHTING CIRCUIT WITH THE AREA THEY OCCUPY. CORRECT
 THIS ACCORDINGLY.
 12. FBC?EC405.5.2 INTERIOR LIGHTING POWER ALLOWANCE.
 THE TOTAL INTERIOR POWER ALLOWANCE IS DETERMINED
 ACCORDING TO THE APPLICABLE TABLES AS INDICATED IN THIS
 SECTION. WITHOUT A FIXTURE SCHEDULE THERE IS NO WAY TO
 VERIFY ALLOWANCE. THOUGH YOU MENTION HI-BAY FIXTURES,
 REMOVE ANY REFERENCE TO EXISTING AS MENTIONED
 PREVIOUSLY. PROVIDE A FIXTURE SCHEDULE AS REQUIRED.
 13. FBC?E C405.2.2. PROVIDE AUTOMATIC LIGHTING SHUTOFF
 FOR THE VARIOUS AREAS PER THIS CODE SECTION. THE NOTE
 ON THE PLANS INDICATES THAT WALL SWITCHES WILL HAVE
 OCCUPANCY SENSORS. I SEE YOU CORRECTED THIS ON THE
 PLANS.
 14. FBC?EC405.2.2.3 DAYLIGHT ZONE CONTROL: DAYLIGHT
 ZONES SHALL BE DESIGNED SUCH THAT LIGHTS IN THE
 DAYLIGHT ZONE ARE CONTROLLED INDEPENDENTLY OF GENERAL
 AREA LIGHTING AND ARE CONTROLLED IN ACCORDANCE WITH
 EITHER SECTION C405.2.2.3.1 OR SECTION C405.2.2.3.2.
 FURTHER LOOKING AT THE PLANS THERE DOES NOT APPEAR TO
 BE A DAYLIGHT ZONE AFFECTED AREA.
 15. FBC?E 405.7.1: AT THE LEAST 50% OF ALL 125?VOLT,
 15? AND 20?AMPERE RECEPTACLES SHALL BE AUTOMATICALLY
 CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN
 OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE
 INSTALLED IN MODULAR PARTITIONS. (SEE ASHRAE STANDARD
 90.1). THIS WOULD NOT APPLY TO YOUR SITUATION.
 16. FIRE ALARM IS REQUIRED UNDER SEPARATE PERMIT AND
 SUBMITTAL
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  
  