Plan Review Notes
Plan Review Notes For Permit 16071099
Permit Number 16071099
Review Stop P
Sequence Number 2
Notes
Date Text
2016-09-10 12:12:181) THIS IS NOTED AS A CHANGE OF OCCUPANCY ON THE PLANS.
 INDICATE THE PREVIOUS OCCCUPANCY ON THE PLANS. WPB
 AMEND. TO FBC 107.2.1. COMPLIANCE WITH FPC SEC.403.1.3
 (POTTY PARITY) MAY BE APPLICABLE.
 2) SHT. A.2 - THE ROOM FINISH SCHEDULE IDENTIFIES THE
 WALL FINISH IN THE MEN'S & WOMEN'S RESTROOMS AS
 "PAINT." COMPLY WITH 2014 FBC SEC.1210.2.1. 1210.2.2.
 3) THE PLANS SHOW INSTANT WATER HEATERS UNDER THE
 LAVATORIES.TEMPERED WATER CONTROL SHALL BE IN
 ACCORDANCE WITH 2014 FPC SEC.607.1.2.
 4) THE GRAB BARS SHALL BE MEASURED FROM THE FINISH
 FLOOR TO THE TOP OF THE GRIPPING SURFACE. FAC SEC.
 609.4.
 5) WHERE ARE THE TOILET PAPER DISPENSERS FOR THE
 ACCESSIBLE COMPARTMENTS? THE DISPENSERS SHALL COMPLY
 WITH FAC SEC. 604.7.
 6) SUBMIT MANUF. SPECIFICATIONS FOR THE INSTANT WATER
 HEATERS. WPB AMEND. TO FBC SEC. 107.2.1.
 7) SHT. A.2 REFERS TO PERMIT #16070659. THIS PERMIT
 NUMBER APPLIES TO 211 DYER ROAD AND IS OBVIOUSLY THE
 WRONG PERMIT NUMBER. SUPPLY THE CORRECT PERMIT NUMBER.
  