| Plan Review Notes For Permit 16071099 |
| Permit Number |
16071099 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-09-10 12:12:18 | 1) THIS IS NOTED AS A CHANGE OF OCCUPANCY ON THE PLANS. | | | INDICATE THE PREVIOUS OCCCUPANCY ON THE PLANS. WPB | | | AMEND. TO FBC 107.2.1. COMPLIANCE WITH FPC SEC.403.1.3 | | | (POTTY PARITY) MAY BE APPLICABLE. | | | 2) SHT. A.2 - THE ROOM FINISH SCHEDULE IDENTIFIES THE | | | WALL FINISH IN THE MEN'S & WOMEN'S RESTROOMS AS | | | "PAINT." COMPLY WITH 2014 FBC SEC.1210.2.1. 1210.2.2. | | | 3) THE PLANS SHOW INSTANT WATER HEATERS UNDER THE | | | LAVATORIES.TEMPERED WATER CONTROL SHALL BE IN | | | ACCORDANCE WITH 2014 FPC SEC.607.1.2. | | | 4) THE GRAB BARS SHALL BE MEASURED FROM THE FINISH | | | FLOOR TO THE TOP OF THE GRIPPING SURFACE. FAC SEC. | | | 609.4. | | | 5) WHERE ARE THE TOILET PAPER DISPENSERS FOR THE | | | ACCESSIBLE COMPARTMENTS? THE DISPENSERS SHALL COMPLY | | | WITH FAC SEC. 604.7. | | | 6) SUBMIT MANUF. SPECIFICATIONS FOR THE INSTANT WATER | | | HEATERS. WPB AMEND. TO FBC SEC. 107.2.1. | | | 7) SHT. A.2 REFERS TO PERMIT #16070659. THIS PERMIT | | | NUMBER APPLIES TO 211 DYER ROAD AND IS OBVIOUSLY THE | | | WRONG PERMIT NUMBER. SUPPLY THE CORRECT PERMIT NUMBER. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|