| 2016-09-07 11:49:22 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16071099 | | | 9/7/16 | | | | | | 1) PLEASE PROVIDE THE SIZES OF THE RTU RETURN AIR DUCTS | | | AND GRILLS. | | | | | | 2) CORRIDOR 104 SHALL NOT BE USED TO CONVEY RETURN AIR | | | TO THE RTU PER SECTION 601.2. PLEASE PROVIDE AN | | | ALTERNATE METHOD. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|