Plan Review Notes
Plan Review Notes For Permit 16071099
Permit Number 16071099
Review Stop E
Sequence Number 2
Notes
Date Text
2016-09-06 17:45:35ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: 501 FERN STREET 101
 JOB ADDRESS: 501 FERN STREET
 DESCRIPTION: GENERAL BUILDING ALTERATIONS TO EXISTING
 BLDG.
 MASTER PERMIT: 16071099
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. PLEASE NOTE THAT PERMIT #13080450 IS NOW EXPIRED AND
 WITHOUT A FINAL ELECTRICAL INSPECTION. THIS PERMIT WILL
 HAVE TO BE REOPENED FOR FINAL INSPECTIONS, OR THE
 ENTIRE SCOPE OF WORK IS INCLUDED IN THIS PERMIT. THAT
 DECISION WILL BE UP TO THE BUILDING OFFICIAL.
 2. ACCORDING TO OUR RECORDS THERE HAVE ONLY BEEN
 SLAB/UNDERGROUND INSPECTIONS FOR THIS PERMIT.
 3. THOUGH NO ROUGH ELECTRICAL INSPECTIONS WERE
 PERFORMED OR RECORDED, THE INITIAL OCCUPANCY WAS NOT
 INTENDED TO BE FOR ASSEMBLY; THEREFORE MINIMUM
 ELECTRICAL REQUIREMENTS FOR THIS TYPE OF OCCUPANCY WERE
 NOT LOOKED FOR IN PLAN REVIEWS.
 4. NEC 518.4: A NOTE WILL BE PLACED ON THE RESUBMITTAL
 REMINDING THE INSPECTORS TO LOOK FOR ANY PVC CONDUIT
 WITHIN THE PREMISES.
 5. NEC 215.5: PROVIDE A SITE SPECIFIC ELECTRICAL RISER
 DIAGRAM INDICATING THE TYPE OF RACEWAYS BEING USED FOR
 THE FEEDERS OF THE TWO ELECTRIC PANELS DESCRIBED. PER
 NEC 518.4, PVC IS PROHIBITED IN ANY ASSEMBLY OCCUPANCY
 UNLESS ENCASED IN 2? OF CONCRETE. YOU SHALL PROVIDE AS
 PART OF THIS RISER SITE SPECIFIC LOAD CALCS TO INCLUDE
 THE LOAD FOR THE 4 INSTANT WATER HEATERS.
 6. NEC 408.4(A): PROVIDE A CIRCUIT DIRECTORY FOR EACH
 OF THE TWO PANELS. ACCORDING TO THE SUBMITTED DIRECTORY
 THERE IS A SINGLE CIRCUIT FOR THE AREA LIGHTING.
 7. NEC 210.62: AT LEAST ONE RECEPTACLE OUTLET SHALL BE
 INSTALLED WITHIN 18? OF THE TOP OF A SHOW WINDOW FOR
 EVERY 12 LINEAR FT. OR MAJOR PORTION THEREOF AREA
 MEASURED HORIZONTALLY.
 8. NEC 210.63 HVAC EQUIPMENT SERVICE OUTLETS. A 125
 VOLT, SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE
 OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR
 THE SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL
 BE LOCATED WITHIN 25 FT. OF THE EQUIPMENT. THIS
 INCLUDES THE RTU UNITS ON THE ROOF.
 9. NEC 422.52 ELECTRIC DRINKING FOUNTAINS. ELECTRIC
 DRINKING FOUNTAINS SHALL BE PROTECTED WITH GROUND-FAULT
 CIRCUIT ?INTERRUPTER PROTECTION (GFI).
 10. NEC 600.5: EACH COMMERCIAL BUILDING AND EACH
 COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS SHALL BE
 PROVIDED WITH AT LEAST ONE 20 AMP DEDICATED OUTLET IN
 AN ACCESSIBLE LOCATION AT EACH ENTRANCE TO EACH TENANT
 SPACE FOR SIGN OR OUTLINE LIGHTING. SERVICE HALLWAYS OR
 CORRIDORS SHALL NOT BE CONSIDERED ACCESSIBLE TO
 PEDESTRIANS. NONE OF THE THREE DOORS COMPLY. THIS
 INCLUDES ALL FOUR DOORS TO THE OUTSIDE.
 11. NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL BE
 FED BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR
 MORE LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY
 BE ON OWN CIRCUIT.
 12. FBC-EC405.5.2 INTERIOR LIGHTING POWER ALLOWANCE.
 THE TOTAL INTERIOR POWER ALLOWANCE IS DETERMINED
 ACCORDING TO THE APPLICABLE TABLES AS INDICATED IN THIS
 SECTION.
 13. FBC-E C405.2.2. PROVIDE AUTOMATIC LIGHTING SHUTOFF
 FOR THE VARIOUS AREAS PER THIS CODE SECTION.
 14. FBC-EC405.2.2.3 DAYLIGHT ZONE CONTROL: DAYLIGHT
 ZONES SHALL BE DESIGNED SUCH THAT LIGHTS IN THE
 DAYLIGHT ZONE ARE CONTROLLED INDEPENDENTLY OF GENERAL
 AREA LIGHTING AND ARE CONTROLLED IN ACCORDANCE WITH
 EITHER SECTION C405.2.2.3.1 OR SECTION C405.2.2.3.2.
 15. FBC-E 405.7.1: AT THE LEAST 50% OF ALL 125-VOLT,
 15- AND 20-AMPERE RECEPTACLES SHALL BE AUTOMATICALLY
 CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN
 OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE
 INSTALLED IN MODULAR PARTITIONS. (SEE ASHRAE STANDARD
 90.1).
 16. FIRE ALARM IS REQUIRED UNDER SEPARATE PERMIT AND
 SUBMITTAL
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  