2016-08-02 17:07:511ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16071099
 8/2/16
  
  
 1) ENERGYGAUGE/ASHRAE 90.1 COMPLIANCE SUBMITTAL: PLEASE
 COMPLETE THE CHECKLIST ON PAGE 1 AND SUBMIT THE
 MANDATORY COMPLIANCE CHECKLIST WITH ALL APPLICABLE
 BOXES CHECKED OFF. PLEASE NOTE THAT ALL CONSTRUCT DATA
 LISTED IN THE INPUT DATA REPORT SHALL BE SHOWN ON THE
 ARCHITECTURAL PLANS.
  
 2) SHEETS A.1, A.2, & M0.2: PLEASE REFER TO SECTION
 303.3 FBC-14 BUILDING AND SHEET A.1. THE ARCHITECT OF
 RECORD HAS CLASSIFIED THE OCCUPANCY AS AN A-2 WHICH IS
 ASSOCIATED WITH RESTAURANT AND DINING FACILITIES,
 BANQUET HALLS, CASINOS ETC. SEE TABLE 403.3 AND REVISE
 THE OUTDOOR AIR CALCULATIONS FOR THE EVENT SPACE (ROOM
 102) WITH THE RATES SPECIFIED FOR DINING ROOMS, AND FOR
 THE STAGING SPACE IN TABLE 403.3. WITH THE RATES
 SPECIFIED FOR KITCHENS. PLEASE NOTE THAT EXHAUST
 VENTILATION IS REQUIRED FOR THE KITCHENS AT A RATE OF
 0.70 CFM PER SQ. FT.
  
 3) M1.1: IDENTIFY THE ROOMS AND SPACES ON THE
 MECHANICAL PLAN.
  
 4) PROVIDE COMPLETE KITCHEN PLANS AND AN EQUIPMENT
 SCHEDULE. PLEASE NOTE THAT SEPARATE PERMITS ARE
 REQUIRED FOR KITCHEN HOOD EXHAUST AND FIRE SUPPRESSION
 SYSTEMS.
  
 5) DEMAND CONTROLLED VENTILATION IS REQUIRED FOR THE
 EVENT SPACE PER SECTION C403.2.5.1. INDICATE ON THE
 PLAN HOW COMPLIANCE WILL BE MET AND PROVIDE DETAILS.
  
 6) M5.1: THE THYBAR CURB NOA #12-0828.02 SPECIFIED ON
 THE PLAN EXPIRED ON 2/10/16. PLEASE CORRECT THE PLAN
 AND SUBMIT A VALID NOA WITH APPROVAL SIGNATURE BY THE
 EOR. PROVIDE COMPLETE ENGINEERING FOR INSTALLATION OF
 THE RTU'S INCLUDING ANCHORING DETAILS FOR MPOUNTING THE
 CURBS TO THE ROOF STRUCTURE.
  