Plan Review Notes
Plan Review Notes For Permit 16071099
Permit Number 16071099
Review Stop B
Sequence Number 1
Notes
Date Text
2016-08-04 15:34:29BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16071099
 ADD: 501 FERN ST. SUITE #102
 CONT: JOHN ROSSI CONSTRUCTION
 TEL: 561-659-5505
 E-MAIL: ROSSI:[email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. AUGUST 04/ 2016
 ACTION: DENIED
  
 1) THE COVER-SHEET A.1 UNDER THE SCOPE OF WORK
 INDICATES THIS IS TO BE A CHANGE OF OCCUPANCY FROM A
 WAREHOUSE TO AN A-2 OCCUPANCY. PLEASE NOTE THE
 COVERSHEET ALSO STATES THIS IS A LEVEL III ALTERATION.
 PLEASE UPDATE THE DRAWING TO A CHANGE OF OCCUPANCY, TO
 BE DESIGNED AND REVIEWED UNDER CHAPTER 10 OF THE
 EXISTING BUILDING CODE. 1001.3.1 PARTIAL CHANGE OF
 OCCUPANCY CLASSIFICATION. WHERE A PORTION OF AN
 EXISTING BUILDING IS CHANGED TO A NEW OCCUPANCY
 CLASSIFICATION, SECTION 1012 SHALL APPLY.
  
 2) THE LIFE SAFETY PLAN CALLS OUT THIS TENANT SPACE IS
 TO BE AN EVENT HALL, THE WORST CASE SCENARIO WILL NEED
 TO TAKE PRECEDENCE. PLEASE NOTE THE COVERSHEET & SHEET
 LS 1 BOTH INDICATE THE OCCUPANT LOAD TO BE REDUCED.
 MAXIMUM EVENT OCCUPANT LOAD OF 225 PERSONS PER SPECIAL
 PROVISIONS EXCEPTION FBC2014 SECTION 1004.1.2. PLEASE
 NOTE THE LIFE SAFETY PLAN DOES NOT SHOW ANY TABLES AND
 CHAIRS SUCH AS AN A2 OCCUPANCY (BANQUET HALL) WOULD
 HAVE. THE CODE REQUIRES THE STRICTER USE OF 7 SQ. FT./
 OCCUPANT WHEN NO TABLES AND CHAIRS ARE SHOWN IN THE
 LIFE SAFETY PLAN. TO DATE NEITHER THE BUILDING OFFICIAL
 NOR THE FIRE MARSHALL HAVE SEEN A LETTER ASKING BOTH
 DEPARTMENTS FOR THE REDUCED LOADING. 7,057/ 7 SQ. FT.
 PER OCC.= 1009 OCCUPANTS.
 7057 SQ. F./ 15 SQ. FT. PER OCC. =471 OCCUPANTS.
  
 PLEASE ALSO NOTE BECAUSE OF THE FLEXIBILITY OF THE
 TENANT SPACE AND THE ISSUES THAT MAY ARISE WITH EACH
 EVENT, THIS EVENT SPACE WILL NEED TO FILE A SPECIAL
 EVENT PERMIT WITH THE FIRE DEPARTMENT SHOWING THE
 USAGE, PROPOSED OCCUPANT LOAD, LAYOUT OF FURNITURE OR
 OTHER OBSTACLES, EGRESS AISLES, FINISHES HUNG ON WALLS
 AND OR FROM CEILINGS, ETC.
  
 3) PLEASE SEE THE NUMBER OF REQUIRED EXITS WOULD BE
 REQUIRED FOR 1009 OCCUPANTS. 1015.1.1 THREE OR MORE
 EXITS OR EXIT ACCESS DOORWAYS. THREE EXITS OR EXIT
 ACCESS DOORWAYS SHALL BE PROVIDED FROM ANY SPACE WITH
 AN OCCUPANT LOAD OF 501 TO 1,000. FOUR EXITS OR EXIT
 ACCESS DOORWAYS SHALL BE PROVIDED FROM ANY SPACE WITH
 AN OCCUPANT LOAD GREATER THAN 1,000. SHOW EGRESS FOR
 THE WORST CASE SCENARIO.
  
 4) PLEASE ALSO NOTE WHEN THE OCCUPANT LOAD WHEN THE
 PRIMARY OCCUPANCY IS PUBLIC ASSEMBLY WITH AN OCCUPANT
 LOAD OF GREATER THAN 300. PLEASE NOTE THIS BUILDING HAS
 2 AREAS OF PUBLIC ASSEMBLY, AREAS A, & C.
 THE RISK CATEGORY FOR THE STRUCTURE INCREASES FROM A
 RISK FACTOR II TO A RISK FACTOR OF III. SEE TABLE
 1604.5 RISK CATEGORY OF BUILDINGS. PLEASE ALSO REVIEW
 FIGURE 1609B FOR RISK CATEGORY III BUILDINGS, 180 MPH
 VULT.
 THE BUILDING WILL NEED TO BE ANALYZED FOR THE HIGHER
 WIND SPEED. SECTION 1007.2. WIND LOADS.
  
  
  
  
 5) THE BUILDING SQUARE FOOT AREA IS OVER THE ALLOWABLE
 6,000 SQ. FT. AREA PER TABLE 503 FOR EITHER AN A2 OR A3
 OCCUPANCY. PLEASE PROVIDE THE AREA AND OR SPRINKLER
 INCREASES TAKEN TO COMPLY WITH THE CODE. 506.1 GENERAL.
 THE BUILDING AREAS LIMITED BY TABLE 503 SHALL BE
 PERMITTED TO BE INCREASED DUE TO FRONTAGE (IF) AND
 AUTOMATIC SPRINKLER SYSTEM PROTECTION (IS) IN
 ACCORDANCE WITH EQUATION 5-1.
  
 6) THE 2014 EXISTING BUILDING CODE SECTION 1013 ENERGY
 CONSERVATION. SEE THE FLORIDA BUILDING CODE, ENERGY
 CONSERVATION. PLEASE BE AWARE THE ENGINEER HAS
 SUBMITTED ENERGY GAUGE ASHRAE 90.1 THE ENERGY COST
 BUDGET METHOD OF COMPLIANCE. THE DOCUMENTS SUBMITTED
 HAVE LITTLE DATA IN REGARDS TO THE THERMAL ENVELOPE
 WHICH WILL NEED TO BE ADDRESSED UNDER 11.ENERGY COST
 BUDGET METHOD 11.1.3 ENVELOPE LIMITATIONS ALSO SEE 11.2
 COMPLIANCE REQUIREMENTS A-C. THE PLANS NEED TO SHOW THE
 COMPLIANCE WITH THE VALUES GIVEN IN THE REPORT.
 INSPECTIONS WILL VERIFY ASSUMPTION?S IN THE FIELD. NO
 INFORMATION PROVIDED FOR ROOFING NOR IS THERE
 ELEVATIONS SHOWING THE SIZES OF THE GLAZED OPENINGS.
  
 6) 2014 FBC-EXISTING BUILDING CODE SECTION 1012.1.3
 CHANGE OF OCCUPANCY CLASSIFICATION BASED ON HAZARD
 CATEGORY. THE RELATIVE DEGREE OF HAZARD BETWEEN
 DIFFERENT OCCUPANCY CLASSIFICATIONS SHALL BE DETERMINED
 IN ACCORDANCE WITH THE CATEGORIES SPECIFIED IN TABLES
 1012.4, 1012.5 AND 1012.6. SUCH A DETERMINATION SHALL
 BE THE BASIS FOR THE APPLICATION OF SECTIONS 1012.4
 THROUGH 1012.7.
  
 6A) THE LIFE SAFETY PLAN WILL NEED TO SHOW HOW THE
 AMOUNT OF OCCUPANTS THAT ARE GOING THROUGH DOORWAYS,
 GIVE THE CLEAR WIDTH, DOWN THE STAIR AND RAMPS AGAIN
 PROVIDE THE WIDTH OF THE RAMP OR STAIR AND AT WHAT
 FACTOR. 2014 FBC-B 1005.3.1 & 1005.3.2.
  
 6B) SHEET LS 1 AND A.3 SHOW A LOBBY BUT NO INFORMATION
 IS GIVEN ON THE STAIRS, RAMP HAND RAILS NOR THE
 GUARDRAILS. PLEASE NOTE THE CITY GAVE A ONE TIME USE ON
 A TEMPORARY EVENT PERMIT FOR THESE ITEMS, BUT IT WAS A
 ONE TIME EVENT. UNDER THAT ONE TIME EVENT THERE WERE NO
 LOADS GIVEN.
 2014 FBC-B 1009.7.2 RISER HEIGHT AND TREAD DEPTH.
 1009.3.1.1 MATERIALS
 1010.1 RAMPS SCOPE
 1010.3 SLOPE
 1010.5 VERTICAL RISE
 1010.7 LANDINGS.
 1010.7.4 CHANGE IN DIRECTION
 1010.8 RAMP CONSTRUCTION
 1010.9 HANDRAILS. & SECTION 1012
 1010.11 GUARDS. & SECTION 1013.
 TABLE 1607.1 LIVE LOADS STAIRS AND RAMPS
 1028.2 ASSEMBLY MAIN EXIT.
 1028.3 ASSEMBLY OTHER EXITS.
 2014 FBC-ACCESS. CODE SECTION 405. RAMPS / STAIRS 504.
 216.1. SIGNS SHALL BE PROVIDED IN ACCORDANCE WITH 216
 AND SHALL COMPLY WITH 703.
 216.9.2 DIRECTIONAL SIGNS.
  
 6C) SHEET A.4 DETAIL A DOES NOT INDICATE WHAT THE
 MATERIALS THIS RAMP IS MADE FROM NOR THE LIVE LOADS FOR
 THE RAMP NOR THE HANDRAIL SYSTEM. 1607.8.1.1
 CONCENTRATED LOAD. HANDRAILS AND GUARDS SHALL ALSO BE
 DESIGNED TO RESIST A CONCENTRATED LOAD OF 200 POUNDS
 (0.89 KN) IN ACCORDANCE WITH SECTION 4.5.1 OF
 ASCE 7.
  
  
 7) SHEET A.5, M1.1 & M5.1 INDICATES 2 NEW ROOF TOP RTU
 UNITS. PLEASE PROVIDE THE STRUCTURAL REINFORCEMENT
 NECESSARY FOR THE NEW OPENINGS IN THE ROOF, POINT
 LOADING OF JOIST REINFORCEMENT, PLEASE PROVIDE THE
 PRODUCT APPROVAL FOR THE ROOF TOP CURBS, AND THE
 ANCHORING SYSTEM FOR BOTH THE CURB TO THE ROOF FRAMING
 AS WELL AS THE RTU UNIT TO THE CURB. FOR ALL ROOF TOP
 EQUIPMENT, CURBS OR A/C STANDS, DETAILED ATTACHMENT TO
 THE ROOF FRAMING & DECK AS WELL AS FROM THE CURB OR
 ROOF STAND TO THE EQUIPMENT ABOVE.
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
  
 8) SHEET A.5, M1.1 & M5.1. FBC-B 1509.6.4 EQUIPMENT AND
 APPLIANCES ON ROOFS OR ELEVATED STRUCTURES.
 WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE
 INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT
 EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE
 PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE
 EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO
 THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH
 ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30 INCHES (762 MM) HIGH OR WALKING ON
 ROOFS HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN
 12 UNITS HORIZONTAL (33-PERCENT SLOPE). PERMANENT
 LADDERS INSTALLED TO PROVIDE THE REQUIRED ACCESS.
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  