| 2016-08-12 15:21:36 | 1) DEFINE THE OCCUPANCY OF THE REAR STRUCTURE IN |
| | ACCORDANCE WITH THE FBC CHAPTER 3. THIS IS NOT AN R-2 |
| | OCCUPANCY, THERE IS EXERCISE EQUIPMENT IN THIS |
| | BUILDING.THIS IS A CHANGE OF OCCUPANCY FROM A |
| | RESIDENTIAL USE AND FULL COMPLIANCE WITH THE 2014 FBC- |
| | ACCESSIBILITY IS REQD. PER 2014 FBC-EXISTING BUILDING |
| | CODE SEC.1012.1.4, 1012.8. |
| | 2) THE BATHING ROOM IN THE REAR STRUCTURE SHALL COMPLY |
| | WITH THE 2014 FAC SEC.604 FOR LOCATION AND REQUIRED |
| | CLEARANCE FOR THE WATER CLOSET,SEE SEC. 606 FOR THE |
| | LAVATORY, SEC. 608 FOR THE SHOWER, GRAB BARS AND |
| | CONTROLS. |
| | 3) A DRINKING FOUNTAIN (MINIMUM OF TWO) IS REQUIRED IN |
| | THE REAR STRUCTURE PER 2014 FBC-PLUMBING, TABLE 403.1 |
| | AND FAC SEC. 211. |
| | 4) THE SINK IN THE GYM SHALL COMPLY WITH FAC SECS.212 & |
| | 606. |
| | 5) IF THE 3-STORY IS DEEMED AN R-2 OCCUPANCY, THEN A |
| | WASHING MACHINE CONNECTION IS REQUIRED IN THE BUILDING |
| | PER FPC TABLE 403.1. |
| | 6) THE KITCHEN SINK IN THE HANDICAPPED ACCESSIBLE |
| | SLEEPING ROOM IN THE 3 STORY SHALL CCOMPLY WITH FAC |
| | SEC.606, 809.3.. A SIDE APPROACH IS NOT PERMITTED |
| | UNLESS ALL THE REQUIREMENTS OF SEC.606.2 (3) (A-C) OF |
| | THE FAC IS MET. PROVIDE VERIFICATION THAT THE KITCHEN |
| | COMPLIES WITH THE EXCEPTION. |
| | 7) THE BATHROOM IN THE HANDICAPPED ACCESSIBLE UNIT |
| | SHALL COMPLY WITH FAC SECS. 809.4, 603 THROUGH 610. |
| | 8) SHT. S-6, DETAIL #03 - THE WATER CLOSET SHALL BE |
| | LOCATED A MINIMUM OF 15 INCHES FROM AN ADJACENT WALL |
| | PER 2014 FPC SEC.405.3.1. |
| | 9) SHT. S-6, DETAIL 01 - THE RANGE /COOKTOP SHALL |
| | COMPLY WITH 2014 FAC SEC. 804.6.4. THE OVEN SHALL |
| | CCOMPLY WITH FAC SEC. 804.6.5. |
| | 10) THE REFRRIGERATOR/FREEZER IN THE ACCESSIBLE UNIT |
| | SHALL COMPLY WITH FAC SEC. 804.6.6. |
| | 11) A 30 INCH BY 60 INCH CLEARANCE SHALL BE PROVIDED |
| | ADJACENT TO THE OPEN FACE OF THE SHOWER IN THE |
| | ACCESSIBLE SHOWER COMPLYING WITH FAC SEC.608.2.2.1. |
| | 12) THE LOCATION OF THE ACCESSIBLE SHOWER CONTROLS |
| | SHALL COMPLY WITH FAC SEC.608.5.2. |
| | 13) THE GRAB BARS IN THE ACCESSIBLE SHOWER SHALL BE |
| | LOCATED IN ACCORDANCE WITH THE FAC SEC. 608.3.2. |
| | 14) A SHOWER SPRAY UNIT SHALL BE PROVIDED IN THE |
| | ACCESSIBLE SHOWER AND COMPLY WITH FAC SEC.608.6. |
| | 15) SHT. S-6 - THE DETAILS FOR THE ADA SHOWER /MOUNTING |
| | HEIGHTS IS FROM AN OUTDATED EDITION OF THE FLORIDA |
| | ACCESSIBILITY CODE. COMPLY WITH THE 2014 EDITION OF |
| | FAC. |
| | 16) SHT. S-6 - SUBMIT AN EXPANDED SANITARY RISER FOR |
| | REVIEW.IT IS EXTREMELY DIFFICULT TO PERFORM A |
| | COMPREHENSIVE ON THE SANITARY RISER THAT HAS BEEN |
| | SUBMITTED. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 17) SUBMIT A WATER RISER DETAIL FOR CHANGES MADE TO THE |
| | EXISTING WATER SYSTEM. WPB AMEND. TO FBC SEC. |
| | 107.3.5.1.3. |
| | 18) SHT. S-11 - THE SINK IN THE DETACHED STRUCTURE IS |
| | NOT PERMITTED ON A WET VENT PER 2014 FPC SEC.912.1. |
| | 19) SIZE ALL THE VENTS ON THE SANITARY RISER FOR THE 3 |
| | STORY STRUCTURE. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805 PLUMBING PLAN REVIEW |