| Plan Review Notes For Permit 16071074 |
| Permit Number |
16071074 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-28 10:39:46 | ELECTRICAL REVIEW NOTES | | | REVIEWED FOR COMPLIANCE WITH: | | | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) | | | | | | JOB NAME: C.A.R.P MENS BUILDING | | | JOB ADDRESS: 1626 OKEECHOBEE ROAD | | | DESCRIPTION: RENOVATION OF 1 STORY BLDG. (COTTAGE) | | | MAST. PERMIT: 16071074 | | | REVISION: | | | | | | | | | 1. CORRECT THE LOAD CALCS AND ELECTRICAL RISER DIAGRAM | | | FOR CODE COMPLIANCE. | | | 2. YOU SHALL PROVIDE A LAUNDRY CIRCUIT PER NEC | | | REQUIREMENTS. | | | 3. PER NEC 760.41 THE FIRE ALARM CIRCUIT SHALL BE | | | PROPERLY IDENTIFIED AND PROTECTED. | | | 4. ALL FIRE ALARM WORK SHALL BE UNDER A SEPARATE PERMIT | | | AND SUBMITTAL. | | | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | | GREATLY APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | PH: 561-805-6746 | | | EMAIL: [email protected] | | | |
|