| 2017-07-14 15:03:50 | 1) SHT. A6.08 - THE CLEAR FLOOR SPACE FOR THE LAVATORY |
| | SHALL BE CENTERED ON THE FIXTURE PER THE FAIR HOUSING |
| | ACCESSIBILITY GUIDELINES.IN ADDITION, PROVIDE THE CLEAR |
| | LENGTH X WIDTH DIMENSIONS OF ALL REQUIRED CLEAR FLOOR |
| | SPACE DIMENSIONS FOR THE FIXTURES PER THE FHAG. |
| | 2) SHT. A6.10 - SHOW THE DIMENSIONS OF THE CLEAR FLOOR |
| | SPACE FOR THE WATER CLOSET IN THE A1 UNIT MODEL. COMPLY |
| | WITH FHAG. |
| | 3) SHT. A 6.10 - UNITS A1 & B1 ARE SHOWN AS A TYPE "A" |
| | & "B" DESIGN SPECIFICATION BATHROOM PER THE FHAG. IF |
| | THESE ARE "UFAS" UNITS, IDENTIFY THEM AS SUCH. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 4) THE LETTTER FROM THE ARCHITECT REGARDING THE TOILET |
| | FACILITIES FOR WORKERS IS VAGUE AND IS UNACCEPTABLE. |
| | REFERENCE IS MADE TO A MAINTENANCE RESTROOM BUT THERE |
| | IS NO MAINTENANCE RESTROOM IN BUILDING #1.SANITARY |
| | FACILITIES FOR WORKERS IN THE MAINTENANCE AND TRASH |
| | AREAS OF BUILDING #1 SHALL BE PROVIDED WITHIN 500 FEET |
| | OF THESE AREAS. 2014 FBC SEC. 403.3.3 |
| | 5) SHT. P4.05 - A URINAL IS NOT PERMITTED ON A WET VENT |
| | THE RISER SHOWS THE URINAL IN THE MEN'S RESTROOM ACROSS |
| | FROM THE EXERCISE ROOM DISCHARGING INTO A VERTICAL WET |
| | VENT ABOVE THE LAVATORY. THE URINAL IS TO BE INSTALLED |
| | ON IT'S OWN STACK & VENTED. 2014 FBC SECS.912.1, |
| | 912.1.1. 3RD REQUEST. |
| | 6) SHT. P2.05B - THE MEN'S AND WOMEN'S RESTROOMS ACROSS |
| | FROM THE EXERCISE ROOM ARE STILL MISLABELED.PLEASE |
| | REVISE. |
| | 7) THE LOCATION OF SANITARY RISERS S/24 & S/25 LOCATED |
| | ACROSS FROM THE LAUNDRY ROOM ON SHT. P2.05B ARE |
| | REVERSED AS TO THE LAYOUT ON SHT. P4.05, REFER TO |
| | BUILDING # II, UNIT B1.2ND REQUEST. |
| | 8) THE DETAIL FOR THE "PLENUM RATED" WATER METERS ON |
| | SHEET P5.00 WILL REQUIRE ADDITIONAL DOCUMENTATION FROM |
| | THE MANUFACTURER CWE. INFORMATION ON THEIR WEBSITE |
| | INDICATES THEY DO NOT MANUFACTURE "PLENUM RATED WATER |
| | METERS". THE MATERIAL COMPOSITION OF THE WATER METERS |
| | SHALL MEET THE SMOKE- DEVELOPED INDEX AND FLAME SPREAD |
| | RATING REQUIREMENTS OF ASTM E84 OR UL 723. THE FLAME |
| | SPREAD INDEX SHALL BE NOT MORE THAN 25 AND THE |
| | SMOKE-DEVELOPED INDEX SHALL NOT BE MORE THAN 50. 2014 |
| | FBC - MECHANICAL SEC. 602.2.1.2ND REQUEST. |
| | 9) SHT. P1.00 - THE ORIENTATION OF BUILDING # II IN |
| | RELATION TO THE POINT OF COMPASS ON THE PLAN DOES NOT |
| | CORRELATE WITH THE ORIENTATION OF BULDING II ON SHT. |
| | P2.05. CLARIFY. 2ND REQUEST. |
| | |
| | NOTE: THE ABOVE CONDITIONS ARE PROVISOS FOR APPROVAL OF |
| | THESE PLANS FOR PLUMBING PLAN REVIEW. REVISED PLANS |
| | SHALL BE SUBMITTED FOR REVIEW AND APPROVAL PRIOR TO THE |
| | ISSUANCE OF THE PLUMBING PERMIT. |
| | T.LARGE, CHIEF PLUMBING INSPECTOR |
| | JULY 14TH, 2017. |
| | |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |