| 2017-07-14 17:29:03 | 3RD REVIEW FBC-2014 MECHANICAL |
| | PERMIT #16071059 |
| | BUILDING #2 |
| | 7/14/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE ENGINEER'S NARRATIVE AND THE CORRECTED PLANS |
| | HAVE ONLY ADDRESSED COMMENT #3 FROM THE 2ND REVIEW. I |
| | AM REPRINTING THE COMMENTS BELOW WITH COMMENT #3 |
| | REMOVED- PLEASE COMPLY. |
| | |
| | 2ND REVIEW FBC-2014 MECHANICAL |
| | PERMIT #16071059 |
| | 6/8/17 |
| | |
| | RESULTS: DENIED. |
| | |
| | 1) THE UPLOADED MECHANICAL RESPONSE NARRATIVE WAS |
| | COPIED FROM THE BUILDING-4 REVIEW (PERMIT #16070880) |
| | AND DID NOT ADDRESS COMMENTS #6-11. |
| | |
| | 2) SHEET M-2.00: THE DRYER EXHAUST DUCTS IN UNITS A1, |
| | A1 ACCESSIBLE, AND A3 ARE NOT PERMITTED TO RUN THROUGH |
| | THE MECHANICAL CLOSETS PER SECTION 504.4. |
| | |
| | 4) THE COMPLIANCE DATA FOR AHU-6 WAS NOT INCLUDED IN |
| | THE ENERGYGAUGETOTAL BUILDING PERFORMANCE SUBMITTAL |
| | FORM. |
| | |
| | 5) PLEASE CORRECT OR REVISE THE PLANS IN ACCORDANCE |
| | WITH 1ST REVIEW COMMENTS #1, 6, 7, 8, 9, 10, 12, & 14 |
| | REPRINTED BELOW: |
| | |
| | 1ST REVIEW COMMENTS. |
| | 8/29/16 |
| | |
| | 1) THE SUBMITTED AC CALCULATION PACKET DOES NOT INCLUDE |
| | THE AHU-3, AHU-4, AHU-A2/CU-2, AHU-A3/CU-3, |
| | AHU-B2/CU-2, AHU-5 (TRASH ROOM) AND AHU-6 (ELEVATOR |
| | VESTIBULE) SYSTEMS- PLEASE PROVIDE. A) THE CALCULATIONS |
| | ARE INCORRECTLY INDICATING MIAMI AS THE LOCATION. B) |
| | REVIEW THE AC SCHEDULE ON M-4.00: THE 4-TON AHU-1 |
| | SYSTEM FOR THE LEASING OFFICE IS ALSO SHOWN AS AN |
| | |
| | 1.5 TON APARTMENT SYSTEM ON SHEET M-02.00- PLEASE |
| | CORRECT. C) REFER TO SECTION C403.2.1 FBC-14 ENERGY |
| | CONSERVATION: A COOLING AND HEATING CALCULATION SHALL |
| | BE SUBMITTED FOR EACH SYSTEM SHOWN ON THE PLAN, AND ALL |
| | SUMMARY CALCULATIONS SUBMITTED BY A REGISTERED ENGINEER |
| | SHALL BEAR THE SIGNATURE AND SEAL OF THE EOR. D) THE |
| | HEATING CAPACITIES OF AHU-1 & 2 (8KW & 10KW IN |
| | |
| | THE EQUIPMENT SCHEDULE) ARE EXCEEDING THE CALCULATED |
| | LOADS AND ARE OVERSIZED- SEE SECTION C403.2.2 FBC-14 |
| | ENERGY CONSERVATION. |
| | |
| | 6) SHEET M-1.05: MANY OF THE DUCT CONNECTIONS TO THE |
| | DIFFUSERS IN THE CLUB ROOM ARE NOT SHOWN. |
| | |
| | 7) M-1.05: EXHAUST VENTILATION IS REQUIRED IN THE FOOD |
| | PREP ROOM PER TABLE 403.3 AND SECTION 507.2.2. PROVIDE |
| | A KITCHEN EQUIPMENT PLAN AND SCHEDULE. A) PROVIDE |
| | MAKEUP AIR AND AIR BALANCE CALCULATIONS. |
| | |
| | 8) M-1.05: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | DRYERS IN THE LAUNDRY ROOM- SECTION 504.7. A) PROVIDE |
| | MAKEUP AIR AND AIR BALANCE CALCULATIONS. PLEASE NOTE |
| | THAT IF THE APPLIANCES ARE GAS-FIRED, COMBUSTION AIR |
| | CALCULATIONS WILL BE REQUIRED. |
| | |
| | 9) PROVIDE TRASH ROOM AND ELECTRICAL ROOM EXHAUST |
| | VENTILATION CALCULATIONS, AND HOISTWAY VENTING |
| | CALCULATIONS. |
| | |
| | 10) PROVIDE A REFRIGERANT PIPING RISER AND INCLUDE |
| | PIPING DETAILS- TYPES AND SIZES, TOTAL ALLOWABLE |
| | LENGTHS PER THE MANUFACTURER SPECIFICATIONS, AND TYPE |
| | AND THICKNESSES OF PIPE INSULATIONS. |
| | |
| | 12) WIND LOAD DESIGN FOR ROOTOP AND GROUND-MOUNTED |
| | MECHANICAL EQUIPMENT: THE CU MOUNTING DETAIL ON M-3.00 |
| | IS INDICATING AN INCORRECT WIND SPEED OF150 MPH. PLEASE |
| | PROVIDE CURRENT WIND LOAD DESIGN CRITERIA ON THE PLAN, |
| | AND SUBMIT THE MIAMI-DADE NOA #13-1017.09 LISTED IN THE |
| | DETAIL. PLEASE NOTE THE EOR SHALL PLACE HIS SHOP |
| | DRAWING APPROVAL STAMP AND SIGNATURE ON THE |
| | |
| | NOA AND ALL OTHER NOAS, PRODUCT APPROVALS, OR |
| | MANUFACTURER'S SPECIFICATIONS SUBMITTED AS PART OF THE |
| | PERMIT PACKAGE- INCLUDING THE GREENHECK MOTORIZED |
| | DAMPER AND LOUVER FOR THE HOISTWAY, AND ALL OTHER |
| | OUTSIDE AIR INTAKE AND EXHAUST OUTLET LOUVERS. |
| | |
| | 14) REFER TO SECTION 3006.2 FBC-14 BUILDING AND CLARIFY |
| | IF THERE IS AN ELEVATOR MACHINE ROOM, AND PROVIDE AN |
| | INDEPENDENT VENTILATION OR AIR CONDITIONING SYSTEM. THE |
| | PLANS SHOW AN ELEVATOR VESTIBULE BUT NO EQUIPMENT IS |
| | SHOWN IN THE ROOM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |