| Plan Review Notes For Permit 16071059 |
| Permit Number |
16071059 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-06-16 08:34:11 | APPROVED WITH EXCEPTION. NEED AIC CALCULATION FOR EACH | | | SERVICE PRIOR TO ROUGH INSPECTION TO CONFIRM SIZING OF | | | SERVICE EQUIPMENT. NEC 110.9, 110.10 | | | REVIEWED PER PREVIOUS COMMENTS ONLY WITH ASSISTANCE | | | FROM JAKE LEAHY. |
|