| 2016-08-29 14:20:31 | 1ST REVIEW FBC-2014 MECHANICAL |
| | ROYAL PALM PLACE- BUILDING- 2 |
| | 8/29/16 |
| | |
| | 1) THE SUBMITTED AC CALCULATION PACKET DOES NOT INCLUDE |
| | THE AHU-3, AHU-4, AHU-A2/CU-2, AHU-A3/CU-3, |
| | AHU-B2/CU-2, AHU-5 (TRASH ROOM) AND AHU-6 (ELEVATOR |
| | VESTIBULE) SYSTEMS- PLEASE PROVIDE. B) THE CALCULATIONS |
| | ARE INCORRECTLY INDICATING MIAMI AS THE LOCATION. B) |
| | REVIEW THE AC SCHEDULE ON M-4.00: THE 4-TON AHU-1 |
| | SYSTEM FOR THE LEASING OFFICE IS ALSO SHOWN AS AN |
| | |
| | 1.5 TON APARTMENT SYSTEM ON SHEET M-02.00- PLEASE |
| | CORRECT. B) REFER TO SECTION C403.2.1 FBC-14 ENERGY |
| | CONSERVATION: A COOLING AND HEATING CALCULATION SHALL |
| | BE SUBMITTED FOR EACH SYSTEM SHOWN ON THE PLAN, AND ALL |
| | SUMMARY CALCULATIONS SUBMITTED BY A REGISTERED ENGINEER |
| | SHALL BEAR THE SIGNATURE AND SEAL OF THE ENGINEER. SEE |
| | ALSO SECTION |
| | |
| | C407.5.2.3 IF SUBMITTING A TOTAL BUILDING PERFORMANCE |
| | ENERGY COMPLIANCE METHOD. C) THE HEATING CAPACITIES OF |
| | AHU-1 & 2 (8KW & 10KW IN THE EQUIPMENT SCHEDULE) ARE |
| | EXCEEDING THE CALCULATED LOADS AND ARE OVERSIZED- SEE |
| | SECTION C403.2.2 FBC-14 ENERGY CONSERVATION. |
| | |
| | 2) SHEETS M-2.00, M-2.01, & M-400: THE SPLIT AC |
| | SCHEDULE DOES NOT INCLUDE THE AHU-2, AHU-3, AHU-B2, & |
| | AHU-B3 SYSTEMS. |
| | |
| | 3) SHEETS M2.00 & M-2.01: THE EXCEPTION UNDER SECTION |
| | 504.6.1 THAT ALLOWED THE USE OF DRYER BOOSTER FANS HAS |
| | BEEN REMOVED FROM THE FBC-14 MECHANICAL CODE. PLEASE |
| | SUBMIT MANUFACTURER'S SPECIFICATIONS AND EXHAUST VENT |
| | INSTALLATION INSTRUCTIONS. |
| | |
| | 4) THE PROPOSED BUILDING SHALL BE IN COMPLIANCE WITH |
| | THE FBC-14 ENERGY CONSERVATION CODE. REFER TO SECTIONS |
| | C101.2, C101.5, AND C401.2 AND SUBMIT COMPLIANCE |
| | MATERIALS AND FORMS. |
| | |
| | 5) PROVIDE EQUIPMENT SCHEDULES FOR THE APARTMENT |
| | OUTSIDE AIR FANS AND MOTORIZED DAMPERS, AND PROVIDE |
| | CLEARANCE DISTANCE MEASUREMENTS FOR ALL AIR INTAKES- |
| | SECTION 401.4 |
| | |
| | 6) SHEET M-1.05: MANY OF THE DUCT CONNECTIONS TO THE |
| | DIFFUSERS IN THE CLUB ROOM ARE NOT SHOWN. |
| | |
| | 7) M-1.05: EXHAUST VENTILATION IS REQUIRED IN THE FOOD |
| | PREP ROOM PER TABLE 403.3 AND SECTION 507.2.2. PROVIDE |
| | A KITCHEN EQUIPMENT PLAN AND SCHEDULE. A) PROVIDE |
| | MAKEUP AIR AND AIR BALANCE CALCULATIONS. |
| | |
| | 8) M-1.05: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | DRYERS IN THE LAUNDRY ROOM- SECTION 504.7. A) PROVIDE |
| | MAKEUP AIR AND AIR BALANCE CALCULATIONS. PLEASE NOTE |
| | THAT IF THE APPLIANCES ARE GAS-FIRED, COMBUSTION AIR |
| | CALCULATIONS WILL BE REQUIRED. |
| | |
| | 9) PROVIDE TRASH ROOM AND ELECTRICAL ROOM EXHAUST |
| | VENTILATION CALCULATIONS, AND HOISTWAY VENTING |
| | CALCULATIONS. |
| | |
| | 10) PROVIDE A REFRIGERANT PIPING RISER AND INCLUDE |
| | PIPING DETAILS- TYPES AND SIZES, TOTAL ALLOWABLE |
| | LENGTHS PER THE MANUFACTURER SPECIFICATIONS, AND TYPE |
| | AND THICKNESSES OF PIPE INSULATIONS. |
| | |
| | 11) PROVIDE UL FIRESTOPPING ASSEMBLIES FOR PIPE |
| | PENETRATIONS. |
| | |
| | 12) WIND LOAD DESIGN FOR ROOTOP AND GROUND-MOUNTED |
| | MECHANICAL EQUIPMENT: THE CU MOUNTING DETAIL ON M-3.00 |
| | IS INDICATING AN INCORRECT WIND SPEED OF150 MPH. PLEASE |
| | PROVIDE CURRENT WIND LOAD DESIGN CRITERIA ON THE PLAN, |
| | AND SUBMIT THE MIAMI-DADE NOA #13-1017.09 LISTED IN THE |
| | DETAIL. PLEASE NOTE THE EOR SHALL PLACE HIS SHOP |
| | DRAWING APPROVAL STAMP AND SIGNATURE ON THE |
| | |
| | NOA AND ALL OTHER NOAS, PRODUCT APPROVALS, OR |
| | MANUFACTURER'S SPECIFICATIONS SUBMITTED AS PART OF THE |
| | PERMIT PACKAGE- INCLUDING THE GREENHECK MOTORIZED |
| | DAMPER AND LOUVER FOR THE HOISTWAY, AND ALL OTHER |
| | OUTSIDE AIR INTAKE AND EXHAUST OUTLET LOUVERS. |
| | |
| | 13) REFER TO SECTION 306.5 AND PROVIDE DETAILS FOR THE |
| | LADDER THAT IS PROVIDING ACCESS TO THE ROOF HATCH. |
| | |
| | 14) REFER TO SECTION 3006.2 FBC-14 BUILDING AND CLARIFY |
| | IF THERE IS AN ELEVATOR MACHINE ROOM, AND PROVIDE AN |
| | INDEPENDENT VENTILATION OR AIR CONDITIONING SYSTEM. THE |
| | PLANS SHOW AN ELEVATOR VESTIBULE BUT NO EQUIPMENT IS |
| | SHOWN IN THE ROOM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |