| 2017-07-14 15:45:03 | 3RD REVIEW FBC-2014 MECHANICAL |
| | PERMIT #16071058 |
| | BUILDING #3 |
| | 7/14/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE ENGINEER'S NARRATIVE AND THE CORRECTED PLANS |
| | HAVE ONLY ADDRESSED COMMENT #3 FROM THE 2ND REVIEW. I |
| | AM REPRINTING THE COMMENTS BELOW WITH COMMENT #3 |
| | REMOVED- PLEASE COMPLY. |
| | |
| | 2ND REVIEW FBC-2014 MECHANICAL |
| | PERMIT #16071058 |
| | 6/8/17 |
| | |
| | 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS- MISSING |
| | DOCUMENTS: THE SUBMITTED AC CALCULATION PACKET DOES NOT |
| | INCLUDE THE AHU-A2/CU-2, AHU-A3/CU-3, & AHU-B2/CU-2, |
| | SYSTEMS, AND ARE LISTING MIAMI AS THE LOCATION. A) |
| | REVIEW THE AC SCHEDULE ON M-4.00 AS THE 4-TON SYSTEM |
| | AHU-1 SYSTEM DOES NOT MATCH THE AHU-1 SYSTEM SHOWN ON |
| | SHEET M-2.00 IN TERMS OF CAPACITY. B) |
| | |
| | REFER TO SECTION C403.2.1 FBC-14 ENERGY CONSERVATION. A |
| | COOLING AND HEATING CALCULATION SHALL BE SUBMITTED FOR |
| | EACH SYSTEM SHOWN ON THE PLAN, AND ALL SUMMARY |
| | CALCULATIONS SUBMITTED BY A REGISTERED ENGINEER SHALL |
| | BEAR THE SIGNATURE AND SEAL OF THE ENGINEER. |
| | |
| | 2) SHEET M-2.00: THE DRYER EXHAUST DUCTS IN UNITS A1, |
| | A1 ACCESSIBLE, AND A3 ARE NOT PERMITTED TO RUN THROUGH |
| | THE MECHANICAL CLOSETS PER SECTION 504.4. |
| | |
| | 4) MISSING DOCUMENTS: PROVIDE ENERGY COMPLIANCE FORM |
| | R405-2014 FOR UNIT A1, AND FOR ENTIRE BUILDING #3. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |