| 2016-08-18 15:02:25 | PERMIT #16070916 906 17TH STREET - 68 UNITS (BUILDING |
| | 1) |
| | PERMIT #16071059 808 17TH STREET - 45 UNITS (BUILDING |
| | 2) |
| | PERMIT #16071058 811 15TH STREET - 6 UNITS (BUILDING 3) |
| | PERMIT #16070880 805 15TH STREET - 6 UNITS (BUILDING 4) |
| | |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | **VERY IMPORTANT** GENERAL: PER NFPA 241 SECTION |
| | 8.7.2.3, WHERE UNDERGROUND WATER MAINS AND HYDRANTS ARE |
| | TO BE PROVIDED, THEY SHALL BE INSTALLED, COMPLETED, AND |
| | IN SERVICE PRIOR TO CONSTRUCTION WORK. |
| | |
| | GENERAL: INDICATE IF ANY TEMPORARY CONSTRUCTION |
| | TRAILERS ARE INTEDED TO OCCUPY THE SITE: PER NFPA 241 |
| | SECTION 4.2.2: DETACHMENT BETWEEN TEMPORARY STRUCTURES, |
| | ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND |
| | PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE |
| | AUTHORITY HAVING JURISDICTION. |
| | PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, |
| | ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2: |
| | TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF |
| | COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE |
| | CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS, |
| | TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1. |
| | PER TABLE 4.2.1: |
| | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 30 FEET |
| | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 35 FEET |
| | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 40 FEET |
| | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 45 FEET |
| | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 50 FEET |
| | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE |
| | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET |
| | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL |
| | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC |
| | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. |
| | |
| | SHEET WS-1 & WS-2: PROVIDE CHAIN WITH LOCK AND TAMPER |
| | SWITCHES FOR SUPERVISING THE BACKFLOW PREVENTER IN THE |
| | OPEN POSITION. PROVIDE LOCKING KNOX CAPS ON FIRE |
| | DEPARTMENT CONNECTIONS. |
| | |
| | SHEET WS-2: NO FIRE MAINS OR FIRE DEPARTMENT |
| | CONNECTIONS PROVIDED FOR BUILDING #3 OR #4. |
| | |
| | SHEET PD-2: THE SOUTH ENTRANCE OFF 15TH STREET IS ONLY |
| | 12 FEET WIDE. PER SECTION 18.2.3.4.1.1 (NFPA 1), FIRE |
| | DEPARTMENT ACCESS ROADS SHALL HAVE A SURFACE DESIGNED |
| | TO ACCOMMODATE FIRE APPARATUS WEIGHING AT LEAST 36 |
| | TONS. ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WIDTH OF |
| | NOT LESS THAN 20 FEET AND AN UNOBSTRUCTED VERTICAL |
| | CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES. |
| | |
| | SHEET LS1.05: THE CLUB ROOM IS AN ASSEMBLY ROOM WITH A |
| | POSSIBLE OCCUPANT LOAD OF 60 TO140 PERSONS DEPENDING |
| | UPON THE OCCUPANT LOAD FACTOR USED. DOOR C WILL NEED TO |
| | HAVE THE SWING REVERSED TO SWING WITH EGRESS. DOORS C |
| | AND D WILL NEED PANIC HARDWARE IF NOT ALREADY EQUIPPED. |
| | |
| | SHEET LS1.05: WHEN OCCUPANTS LEAVE THE EXERCISE ROOM, |
| | WHAT ROUTE IS BEING UTILIZED FOR THE SECONDARY MEANS OF |
| | EGRESS? THE PRIMARY MEANS OF EGRESS IS TO THE EAST. |
| | |
| | EXIT SIGNAGE: SOME OF THE CORRIDORS HAVE AN |
| | INSUFFICIENT AMOUNT OF EXIT SIGNS. PER NFPA 101 SECTION |
| | 7.10.1.5.2 NEW SIGN PLACEMENT SHALL BE SUCH THAT NO |
| | POINT IN AN EXIT ACCESS CORRIDOR IS IN EXCESS OF THE |
| | RATED VIEWING DISTANCE OR 100 FEET, WHICHEVER IS LESS, |
| | FROM THE NEAREST SIGN. |
| | |
| | EMERGENCY LIGHTING: BUILDING 1 APPEARS TO ONLY HAVE |
| | EMERGENCY LIGHTING IN THE STAIRS AND ELEVATOR LOBBY |
| | AREAS. PER NFPA 101 SECTION 30.2.9 EMERGENCY LIGHTING |
| | SHALL BE PROVIDED IN ALL BUILDINGS FOUR OR MORE STORIES |
| | IN HEIGHT, OR WITH MORE THAN 12 DWELLING UNITS, UNLESS |
| | EVERY DWELLING UNIT HAS A DIRECT EXIT TO THE OUTSIDE OF |
| | THE BUILDING AT THE FINISHED GROUND LEVEL. |
| | |
| | SHEET FA-1.00A: ALL OF THE CODES AND STANDARDS |
| | REFERENCED IN NOTE #34 ARE OUT OF DATE. |
| | |
| | FIRE ALARM ADA: NO VISUAL DEVICES PROVIDED IN THE ADA |
| | UNITS. |
| | |
| | FIRE SPRINKLERS: BUILDINGS 3 AND 4 ARE NOT PROTECTED BY |
| | AN AUTOMATIC FIRE SPRINKLER SYSTEM. PER NFPA 101 |
| | SECTION 30.3.5.1 ALL NEW APARTMENT BUILDINGS SHALL BE |
| | PROTECTED THROUGHOUT BY AN APPROVED, SUPERVISED |
| | AUTOMATIC SPRINKLER SYSTEM. |
| | |
| | DISCLAIMER: FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT |
| | ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED |
| | WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL, |
| | ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE |
| | TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT |
| | THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A |
| | CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR |
| | VIOLATIONS OF THIS CODE. REVIEW AND APPROVAL BY THE AHJ |
| | SHALL NOT RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE |
| | RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION |
| | 1.14.4). |
| | |
| | NOTE: SEPARATE PERMITS ISSUED FROM THE BUILDING DEPT. |
| | ARE REQUIRED FOR THE FIRE SPRINKLER, FIRE ALARM, AND |
| | PRIVATE UNDERGROUND FIRE MAINS. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |