| 2016-08-10 11:48:38 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING, |
| | ENERGY CONSERVATION CODES |
| | PERMIT #16071074 |
| | 8/10/16 |
| | |
| | 1) IT IS NECESSARY THAT THE DESIGN PROFESSIONALS REVISE |
| | THE PLANS IN ACCORDANCE WITH THE BUILDING REVIEW |
| | COMMENTS BEFORE A THOROUGH MECHANICAL REVIEW CAN BE |
| | ACCOMPLISHED. BASED ON ALL THE DEFCIENCES IN THE PLAN |
| | CITED IN THE BUILDING COMMENTS, THIS REVIEW WILL BE |
| | CONSIDERED A PRELIMINARY REVIEW AND ADDITIONAL COMMENTS |
| | MAY OCCUR AFTER CORRECTED PLANS HAVE BEEN RESUBMITTED. |
| | |
| | 2) THE SUBMITTED PLANS ARE INDICATING THIS IS A 3-STORY |
| | MULTI-FAMILY BUILDING- PLEASE CORRECT THE APPLICATION |
| | INDICATING A 2-STORY BUILDING. |
| | |
| | 2) REGARDING THE ENERGY AND AC CALCULATION SUBMITTALS, |
| | PLEASE SEE SECTION R103.1.1.1.2 EXCEPTION FBC-14 ENERGY |
| | CONSERVATION, AND PROVIDE DOCUMENTATION OF ENERGY RATER |
| | CERTIFICATION FOR CONNIE'S E-CALCS. |
| | |
| | 3) THE ENERGY CALCULATION FORM R405-2014 MUST BE SIGNED |
| | AND DATED BY THE OWNER/AGENT- SEE SECTION R103.1.1.2. |
| | |
| | 4) THE SUBMITTED FORM R405-2014 INDICATES R30 |
| | INSULATION UNDER THE ATTIC, AND R11 IN THE EXTERIOR |
| | WALLS- PLEASE PROVIDE SECTION CUTS FOR THE EXTERIOR |
| | WALLS AND ATTIC THAT SHOW THE INSULATION THICKNESSES |
| | AND R-VALUES. PLEASE NOTE THAT THE ENERGY CALCULATIONS |
| | ARE INDICATING 1246 SQ. FT. OF R30 INSULATION UNDER |
| | ATTIC. HOW WILL THIS BE ACCOMPLISHED WITH THE ATTIC |
| | APARTMENT THERE? |
| | |
| | 5) SHEET M-1: INDICATE HOW VENTILATION OF ALL ROOMS AND |
| | SPACES WILL BE ACCOMPLISHED, EITHER NATURALLY OR |
| | MECHANICALLY AND PROVIDE CALCULATIONS- SEE SECTIONS |
| | 401.2, 402.1, 402.2, AND TABLE 403.3 FBC-14 MECHANICAL. |
| | |
| | 6) M-1: CU-5 IS SHOWN IN THE EQUIPMENT SCHEDULE AND IN |
| | THE PLANS FOR THE REAR BUILDING, HOWEVER IT IS NOT |
| | INCLUDED IN THE ENERGY OR AC CALCULATIONS. IS THIS |
| | BUILDING AND AC SYSTEM TO BE INCLUDED IN THIS PERMIT OR |
| | UNDER SEPARATE PERMIT?- PLEASE CLARIFY. |
| | |
| | 7) M-1: SHOW THE CONDENSATE DISPOSAL PIPING RUNS AND |
| | INDICATE THE TYPE AND DIAMETER OF PIPING. |
| | |
| | 8) M-1: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR |
| | INSTALLATION OF THE CU'S- SECTIONS 301.15 MECHANICAL, |
| | AND SECTION 1609 FBC-14 BUILDING- BASIC WIND SPEED, |
| | IMPORTANCE FACTOR, EXPOSURE CATEGORY, HEIGHT AND |
| | ADJUSTMENT COEFFICIENT. |
| | |
| | 9) SUBMIT AHRI CERTIFICATES FOR THEDAIKIN SYSTEMS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |