| 2016-07-28 11:20:59 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | JOB NAME: C.A.R.P MENS BUILDING |
| | JOB ADDRESS: 1626 OKEECHOBEE ROAD |
| | DESCRIPTION: RENOVATION OF 2 STORY BLDG.( ACTUALLY A 3 |
| | STORY) |
| | MAST. PERMIT: 16071055 |
| | REVISION: |
| | |
| | 1. NEC 215.5: THE FLOOR PLAN REFLECTS 5 ELECTRICAL |
| | PANELS NOT INCLUDE IN THE ELECTRICAL RISER DIAGRAM. |
| | CORRECT THE RISER DIAGRAM TO SHOW ALL OF THE ELECTRICAL |
| | PANELS AND MAIN DISCONNECTS AS REQUIRED. |
| | 2. NEC 250.94: INCLUDE IN THE RISER DIAGRAM THE |
| | REQUIRED INTER-SYSTEM BONDING TERMINAL. |
| | 3. NEC 110.26(D): PROPER ILLUMINATION IS REQUIRED ABOUT |
| | ELECTRICAL EQUIPMENT. THERE DOES NOT APPEAR TO BE |
| | ADEQUATE LIGHTING WITHIN CLOSE PROXIMITY OF THE |
| | ELECTRICAL PANELS. |
| | 4. YOU SHALL PROVIDE A HOUSE PANEL FOR ALL COMMON AREA |
| | LIGHTING. (EXTERIOR SITE LIGHTING AND THE ILLUMINATION |
| | OF THE PUBLIC/COMMON STAIRWAY). |
| | 5. FIRE ALARM SHALL BE PROVIDED UNDER A SEPARATE PERMIT |
| | AND SUBMITTAL PACKAGE. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |