| 2016-08-03 16:51:28 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16071041 |
| | ADD: 1254 PALM BEACH LAKES BLVD. |
| | CONT: TBD |
| | TEL: 561-577-6874 |
| | E-MAIL: ??????? |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. AUGUST 03/2016 |
| | ACTION: DENIED |
| | |
| | 1) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED. |
| | MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE |
| | TABLE 503). |
| | FIRE SPRINKLERS |
| | FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE |
| | THE FOLLOWING COMPONENTS: |
| | FIRE-RESISTANT SEPARATIONS |
| | FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| | PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE |
| | DOORS |
| | ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| | SITE REQUIREMENTS |
| | ACCESSIBLE ROUTE |
| | TOILET AND BATHING FACILITIES |
| | DRINKING FOUNTAINS |
| | EQUIPMENT- PLAYGROUND |
| | INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| | INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT) |
| | LIGHT AND VENTILATION |
| | SANITATION |
| | |
| | 2) THE PERMIT APPLICATION INDICATES THIS IS A CHANGE OF |
| | USE TO DAYCARE FACILITY. PLEASE PROVIDE TO WHICH |
| | CLASSIFICATION YOU ENTEND TO USE THIS SPACE. DEFINE THE |
| | USE OF SPACE. |
| | |
| | 305.2 GROUP E, DAY CARE FACILITIES. THIS GROUP INCLUDES |
| | BUILDINGS AND STRUCTURES OR PORTIONS THEREOF OCCUPIED |
| | BY MORE THAN FIVE CHILDREN OLDER THAN 21/2 YEARS OF AGE |
| | WHO RECEIVE EDUCATIONAL, SUPERVISION OR PERSONAL CARE |
| | SERVICES FOR FEWER THAN 24 HOURS PER DAY. |
| | |
| | 308.6.1 CLASSIFICATION AS GROUP E. |
| | A CHILD DAY CARE FACILITY THAT PROVIDES CARE FOR MORE |
| | THAN FIVE BUT NO MORE THAN 100 CHILDREN 21/2 YEARS OR |
| | LESS OF AGE, WHERE THE ROOMS IN WHICH THE CHILDREN ARE |
| | CARED FOR ARE LOCATED ON A LEVEL OF EXIT DISCHARGE |
| | SERVING SUCH ROOMS AND EACH OF THESE CHILD CARE ROOMS |
| | HAS AN EXIT DOOR DIRECTLY TO THE EXTERIOR, SHALL BE |
| | CLASSIFIED AS GROUP E. |
| | |
| | CHILDREN 2 1/2 YEARS OF AGE OR LESS USUALLY ARE NOT |
| | ABLE TO RECOGNIZE AN EMERGENCY SITUATION, MAY NOT |
| | RESPOND APPROPRIATELY OR MAY NOT BE ABLE TO EGRESS |
| | WITHOUT ASSISTANCE; THUS FACILITIES THAT HAVE MORE THAN |
| | 5 CHILDREN 2 1/2 YEARS OF AGE OR LESS ARE CLASSIFIED AS |
| | CHILD CARE FACILITIES AND CONSIDERED TO BE GROUP I-4. |
| | |
| | 308.6 INSTITUTIONAL GROUP I-4, DAY CARE FACILITIES. |
| | THIS GROUP SHALL INCLUDE BUILDINGS AND STRUCTURES |
| | OCCUPIED BY MORE THAN FIVE PERSONS OF ANY AGE WHO |
| | RECEIVE CUSTODIAL CARE FOR FEWER THAN 24 HOURS PER DAY |
| | BY PERSONS OTHER THAN PARENTS OR GUARDIANS, RELATIVES |
| | BY BLOOD, MARRIAGE OR ADOPTION, AND IN A PLACE OTHER |
| | THAN THE HOME OF THE PERSON CARED FOR. THIS GROUP SHALL |
| | INCLUDE, BUT NOT BE LIMITED TO, THE FOLLOWING: |
| | CHILD DAY CARE |
| | ADULT DAY CARE |
| | |
| | 3) 2014 FBC-B 1015.6 DAY CARE MEANS OF EGRESS. DAY CARE |
| | FACILITIES, ROOMS OR SPACES WHERE CARE IS PROVIDED FOR |
| | MORE THAN 10 CHILDREN THAT ARE 21/2 YEARS OF AGE OR |
| | LESS, SHALL HAVE ACCESS TO NOT LESS THAN TWO EXITS OR |
| | EXIT ACCESS DOORWAYS. |
| | |
| | 4) 2014 FBC-B 466.2 CLOSET DOORS. EVERY CLOSET DOOR |
| | LATCH SHALL BE SUCH THAT CLIENTS CAN OPEN THE DOOR FROM |
| | INSIDE THE CLOSET. |
| | |
| | 5) 2014 FBC-B 466.3 BATHROOM DOORS. EVERY BATHROOM DOOR |
| | LOCK SHALL BE DESIGNED TO PERMIT OPENING OF THE LOCKED |
| | DOOR FROM THE OUTSIDE IN AN EMERGENCY. THE OPENING |
| | DEVICE SHALL BE READILY ACCESSIBLE TO THE STAFF. |
| | |
| | 6) PLEASE SHOW CODE COMPLIANCE WITH 466.7 DETECTION AND |
| | ALARM SYSTEMS. DAY CARE OCCUPANCIES SHALL BE PROVIDED |
| | WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH SECTION 907 |
| | AND THIS SECTION, 466.7.1 & 466.7.1.1. |
| | |
| | 7) 2014 FBC-B 466.7.2 DETECTION. A SMOKE DETECTION |
| | SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72, |
| | WITH PLACEMENT OF DETECTORS IN EACH STORY IN FRONT OF |
| | DOORS TO THE STAIRWAYS AND IN THE CORRIDORS OF ALL |
| | FLOORS OCCUPIED BY THE DAY CARE OCCUPANCY. DETECTORS |
| | ALSO SHALL BE INSTALLED IN LOUNGES, RECREATION AREAS |
| | AND SLEEPING ROOMS IN THE DAY CARE OCCUPANCY. |
| | |
| | 8) 2014 FBC-B 466.8 CORRIDORS. EVERY INTERIOR CORRIDOR |
| | SHALL BE CONSTRUCTED OF WALLS HAVING NOT LESS THAN A |
| | 1-HOUR FIRE-RESISTANCE RATING. |
| | EXCEPTION: 1. IN BUILDINGS PROTECTED THROUGHOUT BY AN |
| | APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH SECTIONS 901.6 AND 903.3.1.1, CORRIDOR |
| | WALLS SHALL NOT BE REQUIRED TO BE RATED, PROVIDED THAT |
| | SUCH WALLS FORM SMOKE PARTITIONS IN ACCORDANCE WITH |
| | SECTION 710. |
| | EXCEPTION: 2. 2. WHERE THE CORRIDOR CEILING IS AN |
| | ASSEMBLY HAVING 1-HOUR FIRE-RESISTANCE RATING WHERE |
| | TESTED AS A WALL, THE CORRIDOR WALLS SHALL BE PERMITTED |
| | TO TERMINATE AT THE CORRIDOR CEILING. |
| | |
| | 9) ) PLEASE NOTE THE FBC-B CHAPTER 468 SECTION OF THE |
| | CODE ALSO DEALS WITH SCHOOLS AND WOULD NEED TO BE |
| | REVIEWED FOR CODE COMPLIANCE. |
| | 9A) 468.2.2 PLAYGROUNDS AND EQUIPMENT. |
| | PLAYGROUNDS AND EQUIPMENT SHALL BE SAFE, STRUCTURALLY |
| | SOUND, VERMIN PROOF, AND SHALL NOT HAVE JAGGED OR SHARP |
| | PROJECTIONS. PLAYGROUND EQUIPMENT SHALL BE ANCHORED TO |
| | SUITABLE FOUNDATIONS TO PREVENT TOPPLING OR |
| | DISLODGEMENT. CUSHIONING MATERIALS SUCH AS MATS, WOOD |
| | CHIPS, OR SAND SHALL BE USED UNDER CLIMBING EQUIPMENT, |
| | SLIDES, AND SWINGS. |
| | |
| | 9B) 468.2.3 OUTDOOR WASTE CONTAINERS. A SMOOTH |
| | NONABSORBENT SURFACE SHALL BE PROVIDED FOR OUTDOOR |
| | WASTE CONTAINERS. |
| | |
| | 9C) 468.3.4 DIAPER CHANGING STATIONS. A DIAPER CHANGING |
| | STATION SHALL BE LOCATED IN OR ADJACENT TO ANY |
| | CLASSROOM WHERE CHILDREN WEARING DIAPERS ARE IN |
| | ATTENDANCE. A HAND WASHING LAVATORY SHALL BE PROVIDED |
| | WITHIN THE CHANGING STATION AREA. ACCESS SHALL BE |
| | PROVIDED TO THE LAVATORY WITHOUT OPENING DOORS OR |
| | TOUCHING A HANDLE. |
| | |
| | 9D) 468.3.5.2 TEACHER TOILETS. FACULTY AND STAFF |
| | TOILETS SHALL BE SEPARATE FROM STUDENT TOILETS. |
| | |
| | 9E) 468.3.5.5 WALLS. WALLS IN TOILET ROOMS SHALL BE |
| | IMPERVIOUS TO A HEIGHT OF AT LEAST 4 FEET (1219 MM) |
| | ABOVE THE FLOOR. WALLS IN KITCHENS, SCULLERIES, CAN |
| | WASH AREAS, AND SHOWER ROOMS SHALL BE IMPERVIOUS TO A |
| | HEIGHT OF AT LEAST 6 FEET (1829 MM) ABOVE THE FLOOR. |
| | TOILET AND SHOWER PARTITIONS SHALL BE IMPERVIOUS. |
| | |
| | 4F) 2014 FBC-ACCESS. CODE 604.1 GENERAL. WATER CLOSETS |
| | AND TOILET COMPARTMENTS SHALL COMPLY WITH 604.2 THROUGH |
| | 604.8. EXCEPTION: WATER CLOSETS AND TOILET COMPARTMENTS |
| | FOR CHILDREN?S USE SHALL BE PERMITTED TO COMPLY WITH |
| | 604.9. 604.9 WATER CLOSETS AND TOILET COMPARTMENTS FOR |
| | CHILDREN?S USE. |
| | WATER CLOSETS AND TOILET COMPARTMENTS FOR CHILDREN?S |
| | USE SHALL COMPLY WITH 604.9. |
| | |
| | 9G)(1)603.2.1 TURNING SPACE. TURNING SPACE COMPLYING |
| | WITH 304 SHALL BE PROVIDED WITHIN THE ROOM. |
| | |
| | 9G)(2) 603.2.2 OVERLAP. REQUIRED CLEAR FLOOR SPACES, |
| | CLEARANCE AT FIXTURES, AND TURNING SPACE SHALL BE |
| | PERMITTED TO OVERLAP. THIS NOTE IS FOR THE SINGLE |
| | BATHROOM, MISSING CLEARANCE AROUND THE WATER CLOSET. |
| | 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE |
| | 60 INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM |
| | THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED |
| | PERPENDICULAR FROM THE REAR WALL. |
| | |
| | 9H) LOCATION OF PORTABLE FIRE EXTINGUISHERS 2014 FBC-B |
| | 906.1 WHERE REQUIRED. |
| | |
| | 10) PLEASE NOTE THIS IS A CHANGE IN OCCUPANCY FROM |
| | MERCANTILE TO EDUCATIONAL. UNDER THE 2014 EXISTING |
| | BUILDING CODE 1012.4 MEANS OF EGRESS. |
| | EXST. BLDG CODE 1012.4.2 MEANS OF EGRESS FOR CHANGE OF |
| | USE TO EQUAL OR LOWER HAZARD CATEGORY. WHEN A CHANGE OF |
| | OCCUPANCY CLASSIFICATION IS MADE TO AN EQUAL OR LESSER |
| | HAZARD CATEGORY (HIGHER NUMBER) AS SHOWN IN TABLE |
| | 1012.4, EXISTING ELEMENTS OF THE MEANS OF EGRESS SHALL |
| | COMPLY WITH THE REQUIREMENTS OF SECTION 905 FOR THE NEW |
| | OCCUPANCY CLASSIFICATION. NEWLY CONSTRUCTED OR |
| | CONFIGURED MEANS OF EGRESS SHALL COMPLY WITH THE |
| | REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | |
| | 2014FBC-B1008.1.10 PANIC AND FIRE EXIT HARDWARE. DOORS |
| | SERVING ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR |
| | MORE IN A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED |
| | WITH A LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR |
| | FIRE EXIT HARDWARE. |
| | |
| | 2014 EXST. BLDG. CODE. 805.4.4.1 SUPPLEMENTAL |
| | REQUIREMENTS FOR PANIC HARDWARE. WHERE THE WORK AREA |
| | EXCEEDS 50 PERCENT OF THE FLOOR AREA, PANIC HARDWARE |
| | SHALL COMPLY WITH SECTION 805.4.4 THROUGHOUT THE FLOOR. |
| | |
| | 11) THE SUBMITTED PLANS INDICATES THE REAR EXIT LEADS |
| | INTO A FENCED EXTERIOR PLAYGROUND WITH A GATE. THERE IS |
| | NO GATE TO GET OUT OF THE REAR EXIT TO THE PUBLIC WAY. |
| | |
| | 2014 FBC-B 1008.2 GATES. GATES SERVING THE MEANS OF |
| | EGRESS SYSTEM SHALL COMPLY WITH THE REQUIREMENTS OF |
| | THIS SECTION. GATES USED AS A COMPONENT IN A MEANS OF |
| | EGRESS SHALL CONFORM TO THE APPLICABLE REQUIREMENTS FOR |
| | DOORS. |
| | |
| | 12) 2014FBC-B1008.1.10 PANIC AND FIRE EXIT HARDWARE. |
| | DOORS SERVING ROOMS OR SPACES WITH AN OCCUPANT LOAD OF |
| | 50 OR MORE IN A GROUP A OR E OCCUPANCY SHALL NOT BE |
| | PROVIDED WITH A LATCH OR LOCK UNLESS IT IS PANIC |
| | HARDWARE OR FIRE EXIT HARDWARE. |
| | |
| | 13) 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF |
| | EGRESS IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM |
| | ANY ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE |
| | SPACE SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF |
| | EGRESS. |
| | |
| | PLEASE PROVIDE HOW CODE COMPLIANCE WILL BE MET FROM THE |
| | REAR EXIT DOOR (EXIT DISCHARGE) TO THE PUBLIC WAY. |
| | |
| | 14) PLEASE NOTE THERE ARE NO DETAILS FOR THE ACCESSIBLE |
| | ELEMENTS SUCH AS REST ROOMS, LAVS, .2014 FBC-ACCESS. |
| | CODE 606.3 HEIGHT OF 34 INCHES TO THE RIM OR COUNTER |
| | SURFACE. |
| | |
| | 15) SHEET A-1.01 THE RESTROOMS IF THIS IS A FACILITY |
| | FOR YOUNG CHILDREN ARE GOING TO BE FACILITIES AGE |
| | APPROPRIATE FACILIIES THAT WILL SHOW COMPLIANCE WITH |
| | THE 2014 FBC-ACCESSIBLITY CODE 604.9. |
| | |
| | 16) ) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |