| Plan Review Notes For Permit 16070980 |
| Permit Number |
16070980 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-09-12 05:10:47 | 1) THE EXISTING DINING AREA SHOWS 67 SEATS AND THE | | | PROPOSED DINING AREA SHOWS 9 NEW SEATS.THIS ADDS UP TO | | | 76 SEATS WITHOUT THE KITCHEN AND OFFICE AREA SO HOW CAN | | | THE OCCUPANT LOAD BE 73 PERSONS? CLARIFY. | | | 2) SUBMIT FLOW CALCULATIONS FOR THE GREASE TRAP. HOW | | | DID YOU ARRIVE AT THIS SIZE GREASE TRAP? 2014 FPC SEC. | | | 1003.3.4. | | | 3) THE PREP SINK SHALL DISCHARGE THROUGH THE GREASE | | | INTERCEPTOR. 2ND REQUEST.FPC 1003.3.1. | | | 4) SUBMIT A DETAIL FOR THE RECIRCULATION SYSTEM | | | CONNECTION TO THE WATER HEATER. COMPLY WITH FPC | | | SEC.607.2, 607.2.2. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|