Plan Review Notes
Plan Review Notes For Permit 16070980
Permit Number 16070980
Review Stop G
Sequence Number 2
Notes
Date Text
2016-09-12 05:20:281) EXPLAIN HOW YOU ARRIVED AT YOUR COMBUSTION AIR RATES
 ON M-1. WHERE ARE YOU GETTING THE 2090 SQUARE FEET
 TOTAL? SUBMIT THE DIMENSIONS OF THE ROOMS BEING USED
 FOR THE CALCULATIONS AND HOW YOU ARRIVED AT THESE
 NUMBERS. WPB AMEND. TO FBC SEC. 107.2.1.
 2) AN AUTOMATIC GAS SHUTOFF VALVE IS REQUIRED ON THE
 GAS LINE TO THE OVEN PER NFPA 96 SEC.10.4.2ND REQUEST.
 3) THE GAS SHALL BE UNDER A SEPARATE PERMIT.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW