| Plan Review Notes For Permit 16070980 |
| Permit Number |
16070980 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-09-12 05:20:28 | 1) EXPLAIN HOW YOU ARRIVED AT YOUR COMBUSTION AIR RATES | | | ON M-1. WHERE ARE YOU GETTING THE 2090 SQUARE FEET | | | TOTAL? SUBMIT THE DIMENSIONS OF THE ROOMS BEING USED | | | FOR THE CALCULATIONS AND HOW YOU ARRIVED AT THESE | | | NUMBERS. WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) AN AUTOMATIC GAS SHUTOFF VALVE IS REQUIRED ON THE | | | GAS LINE TO THE OVEN PER NFPA 96 SEC.10.4.2ND REQUEST. | | | 3) THE GAS SHALL BE UNDER A SEPARATE PERMIT. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|