| Plan Review Notes For Permit 16070980 |
| Permit Number |
16070980 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-27 17:09:50 | 1ST REVIEW MECHANICAL | | | PERMIT #16070980 | | | 7/27/16 | | | | | | 1) SHEET M-1: IT APPEARS THE DUCT SMOKE DETECTOR FOR | | | AHU-4 IS IN THE SUPPLY, HOWEVER IS IS REQUIRED TO BE IN | | | THE RETURN SYSTEM PER SECTION 606.2.1. | | | | | | 2) M-1: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE | | | KITCHEN EXHAUST HOOD AND DUCT, HOWEVER BECAUSE THESE | | | SYSTEMS WILL IMPACT THE MAIN PERMIT PLANS, PLEASE | | | PROVIDE- A) KITCHEN HOOD AND EXHAUST FAN EQUIPMENT | | | SCHEDULES. B) MAKEUP AIR FOR THE SYSTEMS SECTIONS 508.1 | | | INCLUDING COMPLIANCE FOR MAKEUP AIR TEMPERATURE PER | | | SECTION 508.1.1. C) AIR BALANCE CALCULATIONS. | | | | | | 3) M-1: PROVIDE A TYPE II EXHAUST HOOD FOR THE | | | RELOCATED CONVECTION OVEN- SECTION 507.2.2. | | | | | | 4) M-1: INDICATE HOW COMBUSTION AIR WILL BE PROVIDED TO | | | THE NEW GAS-FIRED APPLIANCES- SHOW THE MEANS AND | | | PROVIDE CALCULATIONS PER SECTION 304 FBC-14 FUEL GAS. | | | | | | 5) M-1: SHOW THE O/A CONNECTION FOR THE RELOCATED AHU-1 | | | OR ADD A NOTE. | | | | | | 6) M-1: PROVIDE A CONDENSATE DISPOSAL PLAN FOR AHU-4. | | | | | | 7) M-1: PROVIDE A MECHANICAL ROOF PLAN WITH CLEARANCE | | | MEASUREMENTS FOR AIR INTAKES, AND FROM EQUIPMENT TO | | | ROOF EDGES. | | | | | | 8) M-1: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR | | | MOUNTING THE CONDENSER TO THE EXISTING ROOF STAND- | | | SECTION 301.5. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|