| Plan Review Notes For Permit 16070980 |
| Permit Number |
16070980 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-12 11:48:58 | 1ST REVIEW | | | | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | | | | GAS COMMENTS: | | | | | | 1.SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | | | 2. AN AUTOMATIC FIRE EXTINGUISHING SYSTEM WITH A | | | AUTOMATIC GAS SHUT OFF IS REQUIRED. PER NFPA | | | 96-10.2.4/10.4.1 | | | |
|