| Plan Review Notes For Permit 16070980 |
| Permit Number |
16070980 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-26 11:38:57 | 7434 SOUTH DIXIE HIGHWAY | | | PERMIT #16070980 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | SIGNAGE: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT | | | DOORS WITH EXIT SIGNS. | | | | | | SHEET A-2: STORAGE (#107) DOOR SWING OBSTRUCTS THE PATH | | | OF EGRESS TO THE NEW DOOR. PER NFPA 101 SECTION | | | 7.2.1.4.3 DOOR LEAF ENCROACHMENT - DURING ITS SWING, | | | ANY DOOR LEAF IN A MEANS OF EGRESS SHALL LEAVE NOT LESS | | | THAN ONE-HALF OF THE REQUIRED WIDTH OF AN AISLE, A | | | CORRIDOR, A PASSAGEWAY, OR A LANDING UNOBSTRUCTED AND | | | SHALL PROJECT NOT MORE THAN 7-INCHES INTO THE REQUIRED | | | WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A | | | LANDING, WHEN FULLY OPEN. | | | | | | SHEET A-2: DRY STORAGE (#112) DOOR SWING MAY IMPEDE | | | EGRESS FROM THE EXISTING RESTROOM (#108). | | | | | | SHEET A-2: SUBMIT EQUIPMENT AND INSTALLATION | | | SPECIFICATIONS FOR THE DECK OVEN. | | | | | | SHEET E-2: AN ADDITIONAL COMBINATION EXIT | | | SIGN/EMERGENCY LIGHT IS NEEDED AT THE EXTERIOR DOOR OF | | | OFFICE (#109) TO PREVENT OCCUPANTS FROM HAVING TO | | | TRAVEL THROUGH THE DRY STORAGE ROOM TO EGRESS THE | | | BUILDING. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | | | | |
|