Plan Review Notes
Plan Review Notes For Permit 16070980
Permit Number 16070980
Review Stop E
Sequence Number 1
Notes
Date Text
2016-07-27 13:39:07ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 JOB NAME: DELI EXPANSION
 JOB ADDRESS: 7432 & 7434 S. DIXIE HWY.
 DESCRIPTION: GENERAL ALTERATIONS TO 7432 & 7434 AND
 KITCHEN EXPANSION
 MAST. PERMIT: 16070980
 REVISION:
  
 1. NEC 600.5 REQUIRED BRANCH CIRCUIT: EACH COMMERCIAL
 BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO
 PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP
 DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH
 ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE
 LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE
 CONSIDERED ACCESSIBLE TO PEDESTRIANS. THOUGH THERE IS A
 SIGN OUTLET REFLECTED ON THE PLANS, THE CODE REQUIRES A
 SIGN OUTLET AT EVERY DOOR.
 2. NEC 210.62 SHOW WINDOWS: AT LEAST ONE RECEPTACLE
 OUTLET SHALL BE INSTALLED WITHIN 18? OF THE TOP OF A
 SHOW WINDOW FOR EVERY 12 LINEAR FT. OR MAJOR PORTION
 THEREOF AREA MEASURED.
 3. FBC-B 1011.1: EXITS AND EXIT ACCESS SHALL BE, MARKED
 BY AN APPROVED EXIT SIGN READILY VISIBLE FROM ANY
 DIRECTION OF EGRESS TRAVEL. THE PATH OF EGRESS SHALL BE
 CLEARLY MARKED WHEN NOT READILY VISIBLE. THERE SHALL
 NOT BE MORE 100? BETWEEN EXIT SIGN ALONG THE PATH OF
 EGRESS. THERE IS A REAR DOOR MISSING AN EXIT LIGHT.
 4. NEC 110.26(D) ILLUMINATION: ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THIS LIGHT
 SHALL NOT BE CONTROLLED BY AUTOMATIC MEANS ONLY. PANELS
 A & B DO NOT APPEAR TO HAVE PROPER ILLUMINATION.
 5. FBC-E C405.2.2. PROVIDE AUTOMATIC LIGHTING SHUTOFF
 6. FBC-EC405.2.2.3 DAYLIGHT ZONE CONTROL: DAYLIGHT
 ZONES SHALL BE DESIGNED SUCH THAT LIGHTS IN THE
 DAYLIGHT ZONE ARE CONTROLLED INDEPENDENTLY OF GENERAL
 AREA LIGHTING AND ARE CONTROLLED IN ACCORDANCE WITH
 EITHER SECTION C405.2.2.3.1 OR SECTION C405.2.2.3.2.
 7. FBC-EC405.5.2 INTERIOR LIGHTING POWER ALLOWANCE. THE
 TOTAL INTERIOR POWER ALLOWANCE IS DETERMINED ACCORDING
 TO THE APPLICABLE TABLES AS INDICATED IN THIS SECTION.
 SUBMIT A LIGHTING DENSITY ALLOWANCE CHART.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  