Plan Review Notes
Plan Review Notes For Permit 16070980
Permit Number 16070980
Review Stop B
Sequence Number 1
Notes
Date Text
2016-08-02 09:40:43BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070980
 ADD: 7402 S. DIXIE HWY. SUITE # 7434
 CONT: PRESTIGE CONSTRUCTION
 TEL: 561-844-3563
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. AUGUST 02/ 2016
 ACTION: DENIED
  
 1) SHEET A-2 CODE INFORMATION INDICATES THE 2014
 EXISTING BUILDING CODE. THE PLANS DO NOT MENTION THIS
 IS A PARTIAL CHANGE OF OCCUPANCY. THE PLANS WILL NEED
 TO SHOW COMPLIANCE WITH THE 2014 FBC-EXISTING BUILDING
 CODE 1001.3.1 PARTIAL CHANGE OF OCCUPANCY
 CLASSIFICATION. WHERE A PORTION OF AN EXISTING BUILDING
 IS CHANGED TO A NEW OCCUPANCY CLASSIFICATION, SECTION
 1012 SHALL APPLY.
  
 2) 2014 EXISTING BUILDING CODE 1012.1.4 ACCESSIBILITY.
 ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH SECTION 1012.8.
 2014 EXISTING BUILDING CODE 1012.8 ACCESSIBILITY.
 EXISTING BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR
 OCCUPANCY CLASSIFICATION SHALL COMPLY WITH THE
 PROVISIONS OF THE FLORIDA BUILDING CODE, ACCESSIBILITY.
 PLEASE SHOW A BREAK DOWN LIST OF THE COST ASSOCIATED
 WITH SECTION 202.4.1 DISPROPORTIONATE COST, $110,000.00
 X 20% = $22,000.00 IN VALUE FOR ACCESSIBLE UPGRADES.
 PLEASE REVIEW THE LIST BELOW WHERE THE FUNDS ARE TO BE
 SPENT AND IN WHAT ORDER.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 3) SHEET A2 SHOWS A NEW EGRESS DOOR AT THE REAR OF THE
 TENANT SPACE. ON THE EXTERIOR A NEW DOOR LANDING AND
 RAMPS ARE PROPOSED. PLEASE NOTE THE RAMP PROTRUDES 48
 INCHES FROM THE BUILDING. PLEASE REVIEW THE 2014
 FBC-ACC. CODE SECTION 404.2.4 MANEUVERING CLEARANCES
 AND FIGURE ( E ). FIGURE ( E ) REQUIRES THE RAMP TO
 PROTRUDE 54 INCHES AWAY FROM THE BUILDING AND THE
 LANDING IS TO BE LEVEL FOR 42 INCHES PAST THE LATCH
 SIDE OF THE DOOR WAY. PLEASE NOTE FOR THIS TO BE AN
 ACCESSIBLE EXIT THE EXTERIOR LANDING WILL NEED TO BE
 EXTENDED TO A SIDEWALK AND TO THE PUBLIC WAY (GOOGLE
 MAPS). 2014 FBC-ACCESSIBILITY CODE 207.1 ACCESSIBLE
 MEANS OF EGRESS SHALL COMPLY WITH THE 2003 IBC SECTION
 1007. 2003 IBC-B 1007.1. WHERE 2 OR MORE MEANS OF
 EGRESS IS REQUIRED BY SECTION 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE PORTION OF THE SPACE SHALL BE SERVED BY NOT
 LESS THAN TWO ACCESSIBLE MEANS OF EGRESS.
  
 4A) THE NEW DOOR OPENING # 1 THERE MAY BE 2 CONCERNS
 NOT CLEARLY ADDRESSED IN THE PLANS. THE DOOR SCHEDULE
 DOES INDICATE THE USE OF PANIC HARDWARE AND A CHAIN
 DOOR STOP. PLEASE NOTE IF A DOOR CLOSER IS TO BE
 INSTALLED THEN COMPLIANCE WITH THE ACCESS. CODE FIGURE
 404.2.4.1 ( C ) WOULD REQUIRE 12 INCHES CLEARANCE ON
 THE INTERIOR SIDE OF THE DOOR AT THE LATCH SIDE.
  
 4B) THE OTHER ISSUE IS THE DISTANCE FROM THE DOOR FACE
 ON THE INTERIOR SIDE OF THE DOOR TO THE FINISH WALL AND
 COMPLIANCE WITH SECTION 404.2.4.3.
  
 5) SHEET A2 THE NEW DOOR # 1 PLEASE PROVIDE THE WIND
 DESIGN CRITERIA. 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 5.2. RISK CATEGORY.
  
 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 6A) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: (31)(A)
 EXTERIOR DOORS.
  
 6B) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) SHEET A2 THE PROPOSED CLOSET DOOR # 2 SWINGS INTO
 THE REQUIRED EGRESS PATH, DOORS IN ANY POSITION SHALL
 NOT REDUCE THE REQUIRED WIDTH BY MORE THAN ONE-HALF.
 2014 FBC-B 1005.7.1.
  
 8) SHEET A2 THE EXISTING DOOR THAT LEADS FROM THE
 DINING AREA TO THE REMODELED DISH WASH ROOM IS MISSING
 THE 18INCHES ON THE LATCH SIDE OF THE DOOR. SEE 2014
 ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES.
  
 9A) SHEET A2 PLEASE SHOW COMPLIANCE WITH THE 2014
 ACCESS. CODE SECTION 226. WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 9B) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 9C) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 9D) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES. PLEASE NOTE THE NEWLY
 PROPOSED COUNTERTOP AT 42 INCHES WILL NEED TO SHOW AN
 ACCESSIBLE COUNTER (DISPERSION).
  
 10) SHEET A2. PLEASE INDICATE THE 3 FRONT ENTRY DOORS
 ARE AT GRADE AND WILL MEET THE REQUIREMENTS FOR AN
 ACCESSIBLE ENTRANCE. 2014 FBC-ACCESSIBILITY CODE 207.1
 ACCESSIBLE MEANS OF EGRESS SHALL COMPLY WITH THE 2003
 IBC SECTION 1007. 2003 IBC-B 1007.1. WHERE 2 OR MORE
 MEANS OF EGRESS IS REQUIRED BY SECTION 1014.1 OR 1018.1
 FROM ANY ACCESSIBLE PORTION OF THE SPACE SHALL BE
 SERVED BY NOT LESS THAN TWO ACCESSIBLE MEANS OF EGRESS.
  
 11) PLEASE NOTE SHEET M1 DETAIL FOR AN EXISTING A/C
 CONDENSER STAND AND NEW CONDENSER MOUNTED TO THE STAND.
 PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THE
 ANCHORING OF THE UNIT TO THE STAND. 2014 FBC-B 1604.4
 ANALYSIS. LOAD EFFECTS ON STRUCTURAL MEMBERS AND THEIR
 CONNECTIONS SHALL BE DETERMINED BY METHODS OF
 STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM,
 GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH
 SHORT- AND LONG-TERM MATERIAL PROPERTIES. EVERY
 STRUCTURE SHALL BE DESIGNED TO RESIST THE OVERTURNING
 EFFECTS CAUSED BY THE LATERAL FORCES SPECIFIED IN THIS
 CHAPTER. SEE SECTION 1609 FOR WIND LOADS?
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION