2016-08-23 15:02:52IN A TELEPHONE CONVERSATION WITH THE GENERAL CONTRACTOR
 I WAS INFORMED THAT THE ACTUAL SCOPE OF THIS PERMIT IS
 TO BRING AN UNPERMITTED CONVERSION FROM A GARAGE TO A
 POOL CABANA INTO COMPLIANCE. I INFORMED THE GC THAT
 REGARDLESS OF WHEN THIS WORK WAS PERFORMED, IT IS BEING
 PERMITTED NOW, AND THEREFORE SHALL MEET THE
 REQUIREMENTS OF THE 5TH EDITION OF THE 2014 FBC-R/2011
 NEC.. ELECTRICAL COMMENT WILL FOLLOW:
  
 ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME:
 JOB ADDRESS: 1724 37TH ST.
 DESCRIPTION: LEGALIZING POOL CABANA
 MASTER PERMIT: 16070968
 SUB PERMIT:
  
 BELOW PLEASE FIND THE DEFICIENCIES FOUND WITH THE ABOVE
 MENTIONED ELECTRICAL SUBMITTAL/PLANS.
  
 1. AN ELECTRICAL SUB-PERMIT IS REQUIRED.
 2. REVISE SCOPE OF WORK ON SHEET S1 TO INCLUDE
 ELECTRICAL WORK.
 3. PLANS SHALL BE DRAWN TO SCALE AND SCALE USED
 INDICATED ON PLANS.
 4. PROVIDE A SITE PLAN SHOWING THE LOCATION OF THE FPL
 UTILITY POLE/S SERVING THE PROPERTY. INCLUDE ON PLANS
 THE OVERHEAD SERVICE DROP/S, THE LOCATION OF EVERY
 ELECTRIC METER AND DISCONNECT.
 5. THE WORD ?ROMEX? AS USED IN THIS NOTE IS TO IDENTIFY
 A TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT A TYPE
 OF CABLE, REFER TO CABLE TYPES ?NM?, ?NMC? OR ?NMS?.
 6. NEC 215.5: A RISER DIAGRAM SHOWING FEEDER DETAILS
 ALONG WITH RESPECTIVE LOAD CALCS SHALL BE PROVIDED.
 THIS DIAGRAM SHALL INCLUDE CONDUCTOR SIZING AND
 INSULATION TYPE. FURTHERMORE, IT SHALL BE SITE
 SPECIFIC.
 7. FBC-RE3601.2/NEC230.2: ONE AND TWO FAMILY DWELLINGS
 SHALL BE SERVED BY ONLY ONE SERVICE.
 8. FBC-RE3601.6.2/NEC 230.70(A)(1): THE SERVICE
 DISCONNECTS SHALL BE LOCATED IN A READILY ACCESSIBLE
 LOCATION OUTSIDE OF THE BLDG. OR INSIDE AT THE NEAREST
 POINT OF ENTRY OF THE SERVICE CONDUCTORS.
 9. FBC-RE3601.7/NEC 230.72: THE TWO TO SIX DISCONNECTS
 AS PERMITTED IN 230.71 SHALL BE GROUPED. EACH
 DISCONNECT SHALL BE MARKED TO INDICATE THE LOAD SERVED.
 10. FBC-RE3601.6.2/NEC 240.24: (A) & (B) PANELS SHALL
 BE LOCATED SUCH THAT OVER CURRENT DEVICES ARE
 ACCESSIBLE AND THAT OCCUPANTS SHALL HAVE ACCESS TO OCP
 DEVICES.
 11. FBC-R3706.2/NEC 408.4(A): REQUIRES THAT YOU
 PROVIDE A PANEL SCHEDULE OR CIRCUIT DIRECTORY LEGIBLY
 INDICATING THE SPECIFIC PURPOSE OF EVERY CIRCUIT.
 12. FBC-RE3902.12/NEC 210.12B: ALL BRANCH CIRCUITS THAT
 SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 OUTLETS INSTALLED IN FAMILY ROOMS, DINING ROOMS, LIVING
 ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS AND SIMILAR ROOMS
 OR AREAS SHALL BE PROTECTED BY A COMBINATION TYPE
 ARC-FAULT CIRCUIT INTERRUPTER INSTALLED TO PROVIDE
 PROTECTION OF THE BRANCH CIRCUIT.
 13. FBC-RE 3901/NEC210.52: CODES HAVE SPECIFIC OUTLET
 SPACING AND LOCATION REQUIREMENTS WHICH SHALL BE
 ADHERED TO.
 14. FBC-R303.9 REQUIRED HEATING - WHEN THE WINTER
 DESIGN TEMPERATURE IN TABLE R301.2(1) IS BELOW 60?F
 (16?C), EVERY DWELLING UNIT SHALL BE PROVIDED WITH
 HEATING FACILITIES CAPABLE OF MAINTAINING A MINIMUM
 ROOM TEMPERATURE OF 68?F (20?C) AT A POINT 3 FEET (914
 MM) ABOVE THE FLOOR AND 2 FEET (610 MM) FROM EXTERIOR
 WALLS IN ALL HABITABLE ROOMS AT THE DESIGN TEMPERATURE.
 THE INSTALLATION OF ONE OR MORE PORTABLE SPACE HEATERS
 SHALL NOT BE USED TO ACHIEVE COMPLIANCE WITH THIS
 SECTION
 15. FBC-R404.1 LIGHTING EQUIPMENT (MANDATORY). A
 MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY
 LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH
 EFFICACY LAMPS
 16. FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS:
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER