| Plan Review Notes For Permit 16070968 |
| Permit Number |
16070968 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-27 11:20:42 | ELECTRICAL REVIEW NOTES | | | REVIEWED FOR COMPLIANCE WITH: | | | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) | | | | | | JOB NAME: | | | JOB ADDRESS: 1724 37TH STREET | | | DESCRIPTION: REPLACE OR REPAIR STUDS AND STRAP | | | ACCORDING TO PLANS, INSTALL HARDY BOARD | | | MAST. PERMIT: 16070968 | | | REVISION: | | | | | | 1. REVISE THE SCOPE OF WORK ON THE PERMIT APPLICATION | | | TO INCLUDE THE ELECTRICAL WORK INDICATED ON PLANS. | | | 2. CLARIFY THE ELECTRICAL SCOPE OF WORK ON THE PLANS TO | | | INDICATE WHAT IS BEING DONE. | | | 3. CORRECT THE CODE COMPLIANCE REFERENCE TO THE 2011 | | | EDITION OF THE NEC AND REVISE THE NOTES AND DRAWINGS | | | ACCORDINGLY. | | | 4. SCOPE OF WORK MAY AFFECT THE OUTLET REQUIREMENTS IN | | | THE LIVING ROOM AND KITCHEN AREAS. | | | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | | GREATLY APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | PH: 561-805-6746 | | | EMAIL: [email protected] | | | |
|