2016-10-14 15:32:491ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16070946
 10/14/16
  
 1) 2ND REQUEST FOR COMPLETE VENTILATION CALCULATIONS.
 THE CALCULATIONS ON SHEET M001 ARE INCORRECT AND DO NOT
 INCLUDE THE ISOLATION ROOM, THE SOIL ROOM, THE CLEAN
 ROOM, THE NOUR ROOM, THE NURSES STATION, THE STAFF
 LOUNGE, THE LOBBY, AND THE PLAYROOM - PLEASE REFER TO
 TABLE 7-1 ASHRAE 170 AND SHOW THE DESIGN PARAMTERS FOR
 EACH ROOM OR SPACE ( PLEASE NOTE THAT VENTILATION RATES
 FOR SOME OF THE ROOMS AND AREAS WILL BE FOUND IN TABLE
 403.3 FBC-14 MECHANICAL) . THE AIR CHANGE RATES SHOWN
 FOR THE PATIENT ROOM, THE EXAM ROOM, AND THE MEDS ROOM
 ON M001 ARE INSUFFICENT PER TABLE 7-1.
  
 2) SHEET M131: THERE APPEARS TO BE MANY DAMPERS MISSING
 FOR DUCTS PENETRATING FIRE-RATED WALLS AND SMOKE
 PARTITIONS INCLUDING, BUT NOT LIMITED TO DUCTS
 PENETRATING THE FOLLOWING LIST OF COMMON WALLS: A)
 ISOLATION/CORRIDOR WALL, B) PATIENT ROOM 304/WAITING
 ROOM WALL. C) CORRIDOR/PATIENT ROOM 305 WALL. D)
 MEDS/NURSES STATION E) CORRIDOR/ADA ROOM WALL. F)
 CORRIDOR/EXAM ROOM WALL. G) CORRIDOR/TLT 325A ROOM
 WALL. H) THE O/A DUCTS PENETRATING CORRIDOR/PATIENT
 ROOMS. PLEASE PROVIDE DAMPER SYMBOLS AT THE SPECIFIED
 LOCATIONS AND ANY OTHER LOCATIONS THAT REQUIRE
 PROTECTION FOR THE DUCTS. PLEASE SEE SECTION 607 AND
 PROVIDE EQUIPMENT SCHEDULES FOR THE FIRE AND SMOKE
 DAMPERS, INSTALLATION DETAILS FOR EACH TYPE, AND
 LOCATIONS OF ACCESS PANELS TO DAMPERS (WHERE REQUIRED).
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER