| 2016-08-01 17:04:05 | 1ST REVIEW FBC-14 MECHANICAL, EXISTING BUILDING CODES. |
| | PERMIT #16070946 |
| | 8/1/16 |
| | |
| | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING AND |
| | PROVIDE VENTILATION CALCULATIONS FOR ALL ROOMS AND |
| | SPACES PER TABLE 7-1 ASHRAE STANDARD 170-2008. PROVIDE |
| | A SCHEDULE ON THE PLAN THAT INDICATES THE REQUIRED AND |
| | PROVIDED OUTDOOR AIR CHANGES AND PRESSURE RELATIONSHIPS |
| | FOR EACH ROOM OR AREA TO ADJACENT AREAS. |
| | |
| | 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| | NEW FAN COIL UNITS- SECTION C403.2.1 FBC-14 ENERGY |
| | CONSERVATION. |
| | |
| | 3) SHEETS M131 & M132: DUCTED RETURNS ARE REQUIRED FOR |
| | THE PATIENT ROOMS- SECTION 2.1-8.2.4.1 GUIDELINES FOR |
| | DESIGN AND CONSTRUCTION OF HEALTH CARE FACILITIES, AND |
| | SECTION 6.7.1 ASHRAE STANDARD 170-2008. |
| | |
| | 4) M131 & M132: MOTORIZED DAMPERS ARE REQUIRED FOR THE |
| | OUTDOOR AIR INTAKES TO THE NEW FCU'S- SEE SECTION |
| | C403.2.4.4 FBC-14 ENERGY CONSERVATION. |
| | |
| | 5) M401: PROVIDE EQUIPMENT SCHEDULES FOR AHU3N-1 & |
| | AHU3N-2. REFER TO TABLE C403.2.6 FBC-14 ENERGY |
| | CONSERVATION AND PROVIDE ENERGY RECOVERY VENTILATION |
| | FOR THE SYSTEMS. |
| | |
| | 6) PROVIDE SPECIFICATIONS FOR THE CHILLED AND HOT WATER |
| | PIPING AND PIPING INSULATION- SEE TABLE C403.2.8 FOR |
| | INSULATION COMPLIANCE. |
| | |
| | 7) REFER TO SECTIONS 8.3, 8.5, AND 8.6 ASHRAE STANDARD |
| | 170-2008 AND ADD NOTES ON THE PLANS TO VERIFY |
| | COMPLIANCE WILL BE MET FOR REQUIRED HVAC DOCUMENTS, AND |
| | DUCT CLEANLINESS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |