| 2016-08-10 12:20:54 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET G 001 - THERE IS AN INCORRECT REFERNCE TO A |
| | FIRE CODE. IN THE MIDDLE OF THE PAGE UNDER "FIRE |
| | PROTECTION REQUIREMENT" NFPA 101, 2009 EDITION IS |
| | INDICATED. |
| | |
| | IT SHOULD READ "2012". PLEASE CORRECT. |
| | |
| | |
| | |
| | 2) SHEET G 130 - THERE IS NO INDICATION ON THIS LIFE |
| | SAFETY PLAN OR ANYWHERE ELSE IF THE PROPOSED WING WILL |
| | BE OCCUPIED DURING ANY CONSTRUCTION PERIOD AND/OR |
| | PHASE. |
| | |
| | PLEASE PROVIDE A NOTE OF BRIEF NARRATIVE OF EACH PHASE |
| | INCLUIDNG SPECIFIC EXITING STRATEGY DETAILS FOR ALL |
| | PROPOSED OCCUPANTS ANS EXITS. |
| | |
| | |
| | |
| | 3) SHEET A 0.11 & G 130 - THE LIFE SAFETY PLAN |
| | INDICATES SMOKE BARRIERS AND SMOKE PARTITIONS IN THE |
| | CORRIDOR OF THE PROPOSE PROJECT. THE DOOR SCHEDULE DOES |
| | NOT INDICATE AND PROTECTION FOR ALL THE CORRIDOR DOORS. |
| | |
| | PER NFPA 1, CHAPTER 12 |
| | |
| | 12.8 SMOKE PARTITIONS. |
| | 12.8.1* GENERAL. WHERE REQUIRED ELSEWHERE IN THIS CODE, |
| | SMOKE PARTITIONS SHALL BE PROVIDED TO LIMIT THE |
| | TRANSFER OF SMOKE. [101:8.4.1] |
| | |
| | 12.8.3 OPENING PROTECTIVES. |
| | 12.8.3.1 DOORS IN SMOKE PARTITIONS SHALL COMPLY WITH |
| | 12.8.3.2 THROUGH 12.8.3.5. [101:8.4.3.1] |
| | 12.8.3.2 DOORS SHALL COMPLY WITH THE PROVISIONS OF |
| | 7.2.1 OF NFPA 101. [101:8.4.3.2] |
| | |
| | 12.9 SMOKE BARRIERS. |
| | 12.9.1* GENERAL. WHERE REQUIRED BY CHAPTERS 11 THROUGH |
| | 43 OF NFPA 101, SMOKE BARRIERS SHALL BE PROVIDED TO |
| | SUBDIVIDE BUILDING SPACES FOR THE PURPOSE OF |
| | RESTRICTING THE MOVEMENT OF SMOKE. [101:8.5.1] |
| | |
| | 12.9.4 OPENING PROTECTIVES. |
| | 12.9.4.1* DOORS IN SMOKE BARRIERS SHALL CLOSE THE |
| | OPENING, LEAVING ONLY THE MINIMUM CLEARANCE NECESSARY |
| | FOR PROPER OPERATION, AND SHALL BE WITHOUT LOUVERS OR |
| | GRILLES. THE CLEARANCE UNDER THE BOTTOM OF A NEW DOOR |
| | SHALL BE A MAXIMUM OF ? IN. (19 MM). [101:8.5.4.1] |
| | 12.9.4.2 WHERE REQUIRED BY CHAPTERS 11 THROUGH 43 OF |
| | NFPA 101, DOORS IN SMOKE BARRIERS THAT ARE REQUIRED TO |
| | BE SMOKE LEAKAGE?RATED SHALL COMPLY WITH THE |
| | REQUIREMENTS OF 8.2.2.5 OF NFPA 101. [101:8.5.4.2] |
| | 12.9.4.3 LATCHING HARDWARE SHALL NOT BE REQUIRED ON |
| | DOORS IN SMOKE BARRIERS UNLESS SPECIFICALLY EXEMPTED BY |
| | CHAPTERS 11 THROUGH 43 OF NFPA 101. [101:8.5.4.3] |
| | 12.9.4.4* DOORS IN SMOKE BARRIERS SHALL BE SELF-CLOSING |
| | OR AUTOMATIC-CLOSING IN ACCORDANCE WITH 14.5.4 AND |
| | SHALL COMPLY WITH THE PROVISIONS OF 7.2.1 OF NFPA 101. |
| | [101:8.5.4.4] |
| | |
| | |
| | NFPA 101, CHAPTER 18 |
| | |
| | 18.3.6.3* CORRIDOR DOORS. |
| | 18.3.6.3.1* DOORS PROTECTING CORRIDOR OPENINGS SHALL BE |
| | CONSTRUCTED TO RESIST THE PASSAGE OF SMOKE, AND THE |
| | FOLLOWING ALSO SHALL APPLY: |
| | (1) COMPLIANCE WITH NFPA 80, STANDARD FOR FIRE DOORS |
| | AND OTHER OPENING PROTECTIVES, SHALL NOT BE REQUIRED. |
| | (2) A CLEARANCE BETWEEN THE BOTTOM OF THE DOOR AND THE |
| | FLOOR COVERING NOT EXCEEDING 1 IN. (25 MM) SHALL BE |
| | PERMITTED FOR CORRIDOR DOORS. |
| | (3) DOORS TO TOILET ROOMS, BATHROOMS, SHOWER ROOMS, |
| | SINK CLOSETS, AND SIMILAR AUXILIARY SPACES THAT DO NOT |
| | CONTAIN FLAMMABLE OR COMBUSTIBLE MATERIAL SHALL NOT BE |
| | REQUIRED TO BE CONSTRUCTED TO RESIST THE PASSAGE OF |
| | SMOKE. |
| | |
| | 18.3.7.3 ANY REQUIRED SMOKE BARRIER SHALL BE |
| | CONSTRUCTED IN ACCORDANCE WITH SECTION 8.5 AND SHALL |
| | HAVE A MINIMUM 1-HOUR FIRE RESISTANCE RATING, UNLESS |
| | OTHERWISE PERMITTED BY ONE OF THE FOLLOWING: |
| | |
| | 18.3.7.6* DOORS IN SMOKE BARRIERS SHALL BE SUBSTANTIAL |
| | DOORS, SUCH AS 1? IN. (44 MM) THICK, SOLID-BONDED |
| | WOOD-CORE DOORS, OR SHALL BE OF CONSTRUCTION THAT |
| | RESISTS FIRE FOR A MINIMUM OF 20 MINUTES, AND SHALL |
| | MEET THE FOLLOWING REQUIREMENTS: |
| | (1) NONRATED FACTORY- OR FIELD-APPLIED PROTECTIVE |
| | PLATES, UNLIMITED IN HEIGHT, SHALL BE PERMITTED. |
| | (2) CROSS-CORRIDOR OPENINGS IN SMOKE BARRIERS SHALL BE |
| | PROTECTED BY A PAIR OF SWINGING DOORS OR A |
| | HORIZONTALSLIDING DOOR COMPLYING WITH 7.2.1.14, UNLESS |
| | OTHERWISE PERMITTED BY 18.3.7.7. |
| | (3) THE SWINGING DOORS ADDRESSED BY 18.3.7.6(2) SHALL |
| | BE ARRANGED SO THAT EACH DOOR SWINGS IN A DIRECTION |
| | OPPOSITE FROM THE OTHER. |
| | (4) THE MINIMUM CLEAR WIDTH FOR SWINGING DOORS SHALL BE |
| | AS FOLLOWS: |
| | (A) HOSPITALS AND NURSING HOMES ? 41? IN. (1055 MM) |
| | (B) PSYCHIATRIC HOSPITALS AND LIMITED CARE FACILITIES ? |
| | 32 IN. (810 MM) |
| | (5) THE MINIMUM CLEAR WIDTH OPENING FOR |
| | HORIZONTAL-SLIDING DOORS SHALL BE AS FOLLOWS: |
| | (A) HOSPITALS AND NURSING HOMES ? 6 FT 11 IN. (2110 MM) |
| | (B) PSYCHIATRIC HOSPITALS AND LIMITED CARE FACILITIES ? |
| | 64 IN. (1625 MM) |
| | (6) THE CLEARANCE UNDER THE BOTTOM OF SMOKE BARRIER |
| | DOORS SHALL NOT EXCEED ? IN. (19 MM). |
| | |
| | 18.3.7.8* DOORS IN SMOKE BARRIERS SHALL COMPLY WITH |
| | 8.5.4 AND ALL OF THE FOLLOWING: |
| | (1) THE DOORS SHALL BE SELF-CLOSING OR |
| | AUTOMATIC-CLOSING IN ACCORDANCE WITH 18.2.2.2.7. |
| | (2) LATCHING HARDWARE SHALL NOT BE REQUIRED. |
| | (3) STOPS SHALL BE REQUIRED AT THE HEAD AND SIDES OF |
| | DOOR FRAMES. |
| | (4) RABBETS, BEVELS, OR ASTRAGALS SHALL BE REQUIRED AT |
| | THE MEETING EDGES OF PAIRS OF DOORS. |
| | |
| | 8.5.4 OPENING PROTECTIVES. |
| | 8.5.4.1* DOORS IN SMOKE BARRIERS SHALL CLOSE THE |
| | OPENING, LEAVING ONLY THE MINIMUM CLEARANCE NECESSARY |
| | FOR PROPER OPERATION, AND SHALL BE WITHOUT LOUVERS OR |
| | GRILLES. THE CLEARANCE UNDER THE BOTTOM OF A NEW DOOR |
| | SHALL BE A MAXIMUM OF ? IN. (19 MM). |
| | 8.5.4.2 WHERE REQUIRED BY CHAPTERS 11 THROUGH 43, DOORS |
| | IN SMOKE BARRIERS THAT ARE REQUIRED TO BE SMOKE |
| | LEAKAGE?RATED SHALL COMPLY WITH THE REQUIREMENTS OF |
| | 8.2.2.4. |
| | 8.5.4.3 LATCHING HARDWARE SHALL BE REQUIRED ON DOORS IN |
| | SMOKE BARRIERS, UNLESS SPECIFICALLY EXEMPTED BY |
| | CHAPTERS 11 THROUGH 43. |
| | 8.5.4.4* DOORS IN SMOKE BARRIERS SHALL BE SELF-CLOSING |
| | OR AUTOMATIC-CLOSING IN ACCORDANCE WITH 7.2.1.8 AND |
| | SHALL COMPLYWITH THE PROVISIONS OF 7.2.1. |
| | (5) CENTER MULLIONS SHALL BE PROHIBITED. |
| | |
| | PLEASE PROVIDE FOR THE PROPER RATING WITHIN THE DOOR |
| | SCHEDULE AND CONSTRUCTION FOR CORRIDIOR DOORS. |
| | |
| | |
| | |
| | 4) SHEET A 0.11- THE DOOR SCHEDULE INDICATES NUMBERED |
| | HARDWARE SETS; HOWEVER, NOT HARDWARE SET DETAIL IS |
| | PROVIDE ( OR WAS NOT CLEARLY FOUND/IDENTIFIED) |
| | |
| | PLEASE PROVIDE DETAILS OR DIRECT TO APPLICABLE SHEET. |
| | |
| | |
| | |
| | 5) SHEET A 130 & A 131 - THE TLT DOOR OPENS INTO THE |
| | EGRESS HALLWAY POTENTIONALLY BLOCKING ACCESS TO THE |
| | ROOM EXIT. |
| | |
| | PER SECTION NFPA 101, DOOR SWING DIRECTION, 7.2.1.4.2, |
| | DOOR IS REQUIRED TO SWING IN THE DIRECTION OF EGRESS |
| | TRAVEL FOR AN OCCUPANT LOAD OF 50 OR GREATER PERSONS. |
| | PER NFPA 101 CHAPTER 7, MEANS OF EGRESS |
| | 7.2.1.4.3 DOOR LEAF ENCROACHMENT |
| | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE |
| | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, |
| | OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT |
| | MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A |
| | CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, |
| | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| | EXISTING BUILDING. |
| | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS |
| | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED |
| | WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY |
| | OPEN. |
| | |
| | |
| | PLEASE CORRECT AND/OR PROVIDE JUSTIFICATION OR DOOR |
| | HARWARE TO ENSURE DOOR REMAINS CLOSED. |
| | |
| | |
| | 6) SHEET E 001, 332 & 531 - THERE IS AN INDICATION OF A |
| | FIRE LARM; HOWEVER, THERE IS NO INDICATION THAT THE |
| | FIRE ALARM SHALL REMAIN ACTIVE DURING CONSTRUCTION AND |
| | ALL WORK SHALL BE DONE BY CERTIFIED LIFE SAFETY |
| | CONTRACTORS UNDER SEPARATE SHOP DRAWINGS. |
| | |
| | PLEASE PROVIDE A NOTE OR NARRATIVE. |
| | |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |