Plan Review Notes
Plan Review Notes For Permit 16070942
Permit Number 16070942
Review Stop P
Sequence Number 2
Notes
Date Text
2016-09-28 09:32:521ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT. G-004.00 FIG.#3 CLEARANCE FOR TOILET SHOULD
 SHOW CLEARLY 60" MEASURED FROM SIDE WALL . THE PLAN
 SHOWS 60" WITH ARROW POINTING TOWARD BACK WALL OF
 TOILET PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. SHT.G-004.00 FIG. #5 SHOWS HEIGHT OF LAV AT 34" MIN
 IT SHALL SHOW 34" MAX NOT MIN. PET FBC ACC 606.3
  
 3. COMPLIANCE WITH PREVIOUS COMMENT #3 CAN NOT BE
 CHECKED SHT. A-001 IS MISSING FROM PLAN SET. PER WPB
 AMEND TO FBC 107.2.1
  
 4. 2ND REQUEST PREVIOUS COMMENT DOES NOT COMPLY. SHT.
 A205 - DETAIL #5 - THE COUNTERTOP SHALL BE A MAXIMUM OF
 34 INCHES ABOVE THE FINISH FLOOR. 2014 FAC SEC.606.3.
  
 5. 2ND REQUEST SHT. M2.2 - DRAWING NOTE #2 - THE
 CONDENSATE SHALL NOT DISCHARGE TO THE SANITARY SYSTEM
 PER WPB CODE OF ORDINANCES CHAPT. 90, ART.III, SEC.
 90-126 (5).
 A) NOTE ON SHT. M-2.2 IS UNCLEAR IT INDICATES DISCHARGE
 ON CONDENSATE INTO MOP SINK WHICH IS SANITARY DRAINAGE,
 THEN IT SAYS CONDENSATE SHALL NOT DISCHARGE INTO
 SANITARY PLEASE CLARIFY.
 B) PROVIDE CONDENSATE RISER DIAGRAM SHOWING DISCHARGE
 INTO STORM DRAINAGE. PER WPB AMEND TO FBC 107.2.1
  
  
  