| 2016-08-23 06:41:14 | 1)DRAWING G-004.00 - THE FOLLOWING THREE COMMENTS APPLY |
| | TO THE SAME SHEET. |
| | FIG. #2 - THE HEIGHT OF THE GRAB BAR SHALL BE MEASURED |
| | FROM THE FINISH FLOOR TO THE TOP OF THE GRIPPING |
| | SURFACE PER THE 2014 FAC SEC. 609.4. |
| | FIG.#3 - THE CLEAR FLOOR SPACE FOR THE WATEER CCLOSET |
| | SHALL CCOMPLY WITH THE FAC SEC. 604.3. |
| | FIG.#5 - THE MAXIMUM HEIGHT TO THE TOP OF THE LAVATORY |
| | SHALL BE 34 INCHES. THE DETAIL SHOWS 29 INCHES MINIMUM. |
| | FAC SEC. 606.3. |
| | 2) THE COFFEE MACHINES, ICE MAKERS, ESPRESSO MACHINE, |
| | ETC. SHALL BE EQUIPPED WITH BACKFLOW PREVENTERS IN |
| | ACCORDANCE THE 2014 FPC SEC. 608.3, 608.16.10. |
| | 3) PER TABLE 403.1 OF THE 2014 FPC AND THE OCCUPANT |
| | LOAD SHOWN ON THE PLANS THE TOTAL NUMBER OF SANITARY |
| | FACILITIES REQUIRED FOR THE MALES IS 5 WATER CLOSETS |
| | AND 4 LAVATORIES AND 5 WATER CLOSETS AND 4 LAVATORIES |
| | FOR THE FEMALES. INCLUDING THE EXISTING FACILITIES, THE |
| | SPACE IS DEFICIENT OF ONE WATER CLOSET EACH FOR THE |
| | MALES AND FEMALES AND TWO LAVATORIES EACH FOR THE MALES |
| | AND FEMALES. THE PROPOSED UNISEX TOILET ROOM CAN HELP |
| | SATISFY THE REQUIREMENTS FOR ONE GENDER ONLY. |
| | 4) SHT. A205 - DETAIL #5 - THE COUNTERTOP SHALL BE A |
| | MAXIMUM OF 34 INCHES ABOVE THE FINISH FLOOR. 2014 FAC |
| | SEC.606.3. |
| | 5) SHT. M2.2 - DRAWING NOTE #2 - THE CONDENSATE SHALL |
| | NOT DDISCHARGE TO THE SANITARY SYSTEM PER WPB CODE OF |
| | ORDINANCES CHAPT. 90, ART.III, SEC. 90-126 (5). |
| | 6) SHT. P-2 - IDENTIFY RISERS #1 & #2 ON THE FLOOR |
| | PLAN. |
| | 7) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| | SPECIFICATIONS FOR THE CHRONOMITE WATER HEATEER. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 8) VENTS OTHER THAN STACK VENTS OR VENT STACKS EXCEEDIN |
| | 40 FEET IN DEVELOPED LENGTH SHALL BE INCREASED BY ONE |
| | NOMINAL PIPE SIZE FOR THE ENTIRE DEEVELOPED LENGTH OF |
| | THE VENT PIPE IN ACCORDANCE WITH THE 2014 FPC |
| | SEC.906.2. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |