| Notes |
| Date |
Text |
| 2016-08-05 08:55:28 | 1ST REVIEW FBC- FIFTH EDITION 2014 MECHANICAL, EXISTING | | | BUILDING CODES | | | PERMIT #16070942 | | | 8/5/16 | | | | | | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED CFMS OF OUTDOOR AIR. | | | | | | 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | | NEW HEAT PUMPS. | | | | | | 3) SHEET M-3: PROVIDE THE EFFICIENCY RATINGS OF THE | | | HEAT PUMPS IN THE SCHEDULE- SEETABLE C403.2.3(2) FBC-14 | | | ENERGY CONSERVATION. | | | | | | 4) M-3: PROVIDE THE SCOP FOR THE COMPUTER ROOM AC | | | SYSTEMS CRAC- 15.1 & 15.2- TABLE C403.2.3(10) FBC-14 | | | ENERGY CONSERVATION. | | | | | | 5) M-2.1: PLEASE PLACE A NOTE INDICATING ABOVE CEILING | | | IS A RETURN AIR PLENUM- NO COMBUSTIBLE MATERIALS | | | PERMITTED PER SECTION 602.2.1. | | | | | | 6) M-2.1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE | | | EXISTING AHU. | | | | | | 7) M-4.1 & M-4.2: PLEASE ENLARGE THESE DETAILS SO THE | | | PRINT IS LARGER AND LEGIBLE- #10, 21, 23, 25, 26, 30 & | | | 34. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|