2016-08-05 08:55:281ST REVIEW FBC- FIFTH EDITION 2014 MECHANICAL, EXISTING
 BUILDING CODES
 PERMIT #16070942
 8/5/16
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW HEAT PUMPS.
  
 3) SHEET M-3: PROVIDE THE EFFICIENCY RATINGS OF THE
 HEAT PUMPS IN THE SCHEDULE- SEETABLE C403.2.3(2) FBC-14
 ENERGY CONSERVATION.
  
 4) M-3: PROVIDE THE SCOP FOR THE COMPUTER ROOM AC
 SYSTEMS CRAC- 15.1 & 15.2- TABLE C403.2.3(10) FBC-14
 ENERGY CONSERVATION.
  
 5) M-2.1: PLEASE PLACE A NOTE INDICATING ABOVE CEILING
 IS A RETURN AIR PLENUM- NO COMBUSTIBLE MATERIALS
 PERMITTED PER SECTION 602.2.1.
  
 6) M-2.1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 EXISTING AHU.
  
 7) M-4.1 & M-4.2: PLEASE ENLARGE THESE DETAILS SO THE
 PRINT IS LARGER AND LEGIBLE- #10, 21, 23, 25, 26, 30 &
 34.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER