| 2016-08-23 08:03:12 | RESPONDED TO PHONE CALL, LEFT MESSAGE W/RECEP. MR. AKI |
| | CALLED ME BACK WITH A QUESTION ON THE RECEPTACLE |
| | CONTROL REQUIREMENTS. HE AGREES AND WILL COMPLY. |
| 2016-08-04 16:34:07 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: UBS FINANCIAL SERVICES, INC. |
| | JOB ADDRESS: 525 OKEECHOBEE BLVD., SUITE 1500 |
| | DESCRIPTION: INTERIOR OFFICE BUILD OUT 15TH FLOOR |
| | MASTER PERMIT:16070942 |
| | REVISION: |
| | |
| | 1. LIGHTING SHEET E3.1 IS SO CLUTTERED THAT IT IS VERY |
| | DIFFICULT TO PERCEIVE ROOM DIVIDERS THUS MAKING THE |
| | PLACEMENT OF EMERGENCY LIGHTING DIFFICULT AS WELL. |
| | A) THE AREA BETWEEN GRID LINES 1/5-F/M DOES NOT APPEAR |
| | TO HAVE SUFFICIENT EMERGENCY LIGHTING. |
| | B) ROOMS 15-032, 15-028, 15-026, 15-019, 15-011, |
| | 15-097, 15-081 AND 15-076 AMONG OTHERS NOT IDENTIFIED |
| | MAY REQUIRE EMERGENCY LIGHTING. |
| | 2. FBC-E 405.7.1: AT THE LEAST 50% OF ALL 125-VOLT, 15- |
| | AND 20-AMPERE RECEPTACLES SHALL BE AUTOMATICALLY |
| | CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN |
| | OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE |
| | INSTALLED IN MODULAR PARTITIONS. (SEE ASHRAE STANDARD |
| | 90.1) |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |