| 2016-08-29 09:47:10 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | COMMENTS: |
| | |
| | 1. E1.00-1.01- GENERAL NOTES TO CONSTRUCTION DOCUMENTS: |
| | PLEASE PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| | SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS FOR ALL SITE LIGHTING AND ASSOCIATED |
| | EQUIPMENT, ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT |
| | LIMITED TO FIRE ALARM, ACCESS CONTROLS (GATES), CCTV, |
| | PHONE AND DATA, WIRELESS SYSTEMS, ETC. A NOTE WILL |
| | SUFFICE. |
| | 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3, |
| | 405.7.4 SEE VERBIAGE IN THE CODE REGARDING VOLTAGE DROP |
| | AND COMPLETIONS DOCUMENTS. |
| | 3. E1.00- PROVIDE A NOTE TO POOL TO BE UNDER SEPARATE |
| | PERMIT. |
| | 4. E1.02- DELETE REFERENCE TO MIAMI DADE COUNTY |
| | STANDARDS FOR LIGHTING ILLUMINATION PARKING AREA. |
| | 5. PLEASE ADDRESS FIRE COMMENTS RELATED TO EM LIGHTING |
| | REQUIREMENTS. |
| | 6. PLEASE SHOW AIC CALCULATION BASED ON INFORMATION |
| | PROVIDED BY FPL UTILITY FOR APPROVAL. NEC 110.24 FBC |
| | 107. |
| | 7. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO |
| | INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC |
| | 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE |
| | VERBIAGE IN CODE. |
| | 8. PLEASE CLARIFY FIRE PUMP REFERENCE ON RISER DIAGRAM |
| | FOR A COMPLETE REVIEW, FBC 107.3.5 |
| | 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE |
| | TO CONTACT ME SHOULD YOU HAVE ANY |
| | |
| | |
| | VALENTINO PEREZ |
| | ELECTRICAL PLANS EXAMINER II |