Plan Review Notes
Plan Review Notes For Permit 16070909
Permit Number 16070909
Review Stop B
Sequence Number 2
Notes
Date Text
2016-10-14 07:11:26BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070909
 ADD: 5112 GEORGIA AVE.
 CONT: TD GONE BUILDING
 TEL: 561-436-4047
 E-MAIL; [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. 14/ 2016
 ACTION: DENIED
  
 1) 2ND REQUEST . ORIGINALLY 3 SETS OF PLANS SUBMITTED.
 ON THE RE-SUBMITTAL ONLY 2 SETS OF PLANS WERE
 SUBMITTED. ONLY 2 SOILS REPORTS WERE SUBMITTED. THIS IS
 A RESIDENT INSPECTOR PROJECT REQUIRING 3 SETS OF
 DOCUMENTS. 2014 FLORIDA BUILDING CODE W 2014 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 110.3.9.
 1ST ROUND COMMENTS. FOR RESIDENT INSPECTOR PROJECTS 3
 SETS OF PLANS ARE REQUIRED. ONE FOR CITY RECORD
 RETENTION, ONE FOR THE CONTACTOR AND THE 3RD SET FOR
 THE RESIDENT INSPECTOR. 2014 FLORIDA BUILDING CODE W
 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.1.
  
 2) SEMI-COMPLIED ONLY 2 SETS OF PLANS.
 1ST ROUND OF COMMENTS. THE SHEET A100 DESIGNED BY
 ANGELIO DAVILA # 16639 HAS NOT SIGNED NOR SEALED THE
 ARCHITECTURAL PLANS. PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT. FL ADMIN CODE 61G16.003 ARCHITECTS.
  
 3)COMPLIED
  
 4) COMPLIED
  
 5) 2ND REQUEST. CONTRACTOR AT OWN RISK!!!
 SHEET S1 DETAIL 3 & 4 BOTH SHOW THE USE OF A ROOF TOP
 PRESSURE TREATED 4 X 4. PLEASE NOTE PITCH PANS HAVE NOT
 BEEN USED IN THE CODE FOR SOME TIME NOW. PLEASE REVIEW
 UNDER THE 2014 FBC-B 1509.6.5 AND TABLE 1509.6.5.
 1509.6.5 MECHANICAL UNITS. ROOF MOUNTED MECHANICAL
 UNITS SHALL BE MOUNTED ABOVE THE ROOF SURFACE, OR WHERE
 ROOFING MATERIALS EXTEND BENEATH THE UNIT, ON RAISED
 EQUIPMENT SUPPORTS PROVIDING A MINIMUM CLEARANCE HEIGHT
 IN ACCORDANCE WITH TABLE 1509.6.5.
  
 6) COMPLIED
  
 7) 2ND REQUEST. THE RESPONSE INDICATES THE BUILDING
 PERMIT HAS TO BE ISSUED BEFORE THE FIRE SPRINKLER CAN
 APPLY FOR THEIR PERMIT. 2014 FBC-B 903.2.4.1
 WOODWORKING OPERATIONS. AN AUTOMATIC SPRINKLER SYSTEM
 SHALL BE PROVIDED THROUGHOUT ALL GROUP F-1 OCCUPANCY
 FIRE AREAS THAT CONTAIN WOODWORKING OPERATIONS IN
 EXCESS OF 2,500 SQUARE FEET (232 M2) IN AREA WHICH
 GENERATE FINELY DIVIDED COMBUSTIBLE WASTE OR USE FINELY
 DIVIDED COMBUSTIBLE MATERIALS.
 THIS IS A BUILDING CODE ISSUE THAT HAS TO BE SATISFIED
 BEFORE PERMIT ISSUANCE, THE FIRE SPRINKLER DESIGN
 DOCUMENTS ARE REQUIRED TO BE SUBMITTED REVIEWED AND
 APPROVED BEFORE ISSUANCE OF A PERMIT. A SECOND SET OF
 FIRE SPRINKLER PLANS WILL BE REQUIRED, AND TO SUBMIT
 SEPARATELY UNDER A SEPARATE PERMIT, REVIEW AND
 ASSOCIATED FEES.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 (5) FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
 PRE-ENGINEERED SYSTEMS
  
 NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) WITH RESPECT
 TO EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 1ST ROUND OF COMMENTS. THE ARCHITECTURAL PLANS ARE
 SILENT ABOUT THE REQUIREMENTS FOR FIRE SPRINKLERS IN
 THE RELOCATED DUST COLLECTOR DUCT. 2014 FBC-B 903.2.4.1
 WOODWORKING OPERATIONS. AN AUTOMATIC SPRINKLER SYSTEM
 SHALL BE PROVIDED THROUGHOUT ALL GROUP F-1 OCCUPANCY
 FIRE AREAS THAT CONTAIN WOODWORKING OPERATIONS IN
 EXCESS OF 2,500 SQUARE FEET (232 M2) IN AREA WHICH
 GENERATE FINELY DIVIDED COMBUSTIBLE WASTE OR USE FINELY
 DIVIDED COMBUSTIBLE MATERIALS.
  
 8-10) COMPLIED.
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  