Plan Review Notes
Plan Review Notes For Permit 16070909
Permit Number 16070909
Review Stop M
Sequence Number 1
Notes
Date Text
2016-07-26 07:44:551ST REVIEW MECHANICAL
 PERMIT #16070909
 7/26/16
  
 1) SHEET A100: THE ARCHITECT OF RECORD MUST PLACE HIS
 SIGNATURE AND SEAL ON THE PLANS AS REQUIRED BY SECTION
 481.221(2) FLORIDA STATUTES, AND SECTION 61G1-16.001
 FLORIDA ADMINISTRATIVE CODE.
  
 2) A100: THE DUST COLLECTOR IS IDENTIFIED AS BOTH "NEW"
 AND "RELOCATED". PLEASE CLARIFY. IF THE COLLECTOR IS
 NEW, PLEASE PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN,
 AND SUBMIT MANUFACTURER'S SPECIFICATIONS WITH SHOP
 DRAWING APPROVAL SIGNATURE BY THE ARCHITECT OF RECORD.
  
 3) A100: PLEASE ENLARGE THE MEASUREMENTS SHOWN ON THE
 BETWEEN THE DUST COLLECTOR AND SHAVING HOUSE, AND FROM
 THE TWO STRUCTURES TO WHAT APPEARS TO BE A PROPERTY
 LINE OR RIGHT OF WAY LINE. REFER TO SECTIONS 501.3.1(1)
 & 511.1 AND PROVIDE A CLEARANCE DISTANCE MEASUREMENT TO
 THE EXISTING BUILDING, AND HEIGHT MEASUREMENTS FOR THE
 COLLECTOR, SHAVING HOUSE, AND THE EXISTING BUILDING.
  
 4) A100: SHOW THE POINT OF CONNECTION FOR THE NEW
 EXHAUST DUCT TO THE EXISTING, AND PROVIDE THE LENGTH OF
 THE DUCT RUNS; THE TYPE, SIZE, AND GAGE OF DUCTWORK;
 SPECIFICATIONS FOR DUCT SUPPORTS INCLUDING SPACINGS,
 HEIGHT OF THE DUCTWORK ABOVE THE ROOF.
  
 5) A100: INDICATE IF A NEW, LARGER CAPACITY EXHAUST FAN
 IS TO BE INSTALLED DUE TO THE INCREASED LENGTH OF THE
 DUCT RUN AND PROVIDE A FAN SCHEDULE AND CALCULATIONS IF
 APPLICABLE. OTHERWISE, PLEASE INDICATE THE MAKE AND
 MODEL AND CFM CAPACITY OF THE EXISTING EXHAUST FAN.
  
 6) A100: PROVIDE VENTING DETAILS FOR THE DUST COLLECTOR
 AND SHAVING HOUSE.
  
 7) REFER TO SECTION 301.15 AND PROVIDE WIND LOAD
 ENGINEERING FOR INSTALLATION OF THE DUCT WORK AND DUCT
 WORK SUPPORTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  