| 2016-07-26 07:44:55 | 1ST REVIEW MECHANICAL |
| | PERMIT #16070909 |
| | 7/26/16 |
| | |
| | 1) SHEET A100: THE ARCHITECT OF RECORD MUST PLACE HIS |
| | SIGNATURE AND SEAL ON THE PLANS AS REQUIRED BY SECTION |
| | 481.221(2) FLORIDA STATUTES, AND SECTION 61G1-16.001 |
| | FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 2) A100: THE DUST COLLECTOR IS IDENTIFIED AS BOTH "NEW" |
| | AND "RELOCATED". PLEASE CLARIFY. IF THE COLLECTOR IS |
| | NEW, PLEASE PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN, |
| | AND SUBMIT MANUFACTURER'S SPECIFICATIONS WITH SHOP |
| | DRAWING APPROVAL SIGNATURE BY THE ARCHITECT OF RECORD. |
| | |
| | 3) A100: PLEASE ENLARGE THE MEASUREMENTS SHOWN ON THE |
| | BETWEEN THE DUST COLLECTOR AND SHAVING HOUSE, AND FROM |
| | THE TWO STRUCTURES TO WHAT APPEARS TO BE A PROPERTY |
| | LINE OR RIGHT OF WAY LINE. REFER TO SECTIONS 501.3.1(1) |
| | & 511.1 AND PROVIDE A CLEARANCE DISTANCE MEASUREMENT TO |
| | THE EXISTING BUILDING, AND HEIGHT MEASUREMENTS FOR THE |
| | COLLECTOR, SHAVING HOUSE, AND THE EXISTING BUILDING. |
| | |
| | 4) A100: SHOW THE POINT OF CONNECTION FOR THE NEW |
| | EXHAUST DUCT TO THE EXISTING, AND PROVIDE THE LENGTH OF |
| | THE DUCT RUNS; THE TYPE, SIZE, AND GAGE OF DUCTWORK; |
| | SPECIFICATIONS FOR DUCT SUPPORTS INCLUDING SPACINGS, |
| | HEIGHT OF THE DUCTWORK ABOVE THE ROOF. |
| | |
| | 5) A100: INDICATE IF A NEW, LARGER CAPACITY EXHAUST FAN |
| | IS TO BE INSTALLED DUE TO THE INCREASED LENGTH OF THE |
| | DUCT RUN AND PROVIDE A FAN SCHEDULE AND CALCULATIONS IF |
| | APPLICABLE. OTHERWISE, PLEASE INDICATE THE MAKE AND |
| | MODEL AND CFM CAPACITY OF THE EXISTING EXHAUST FAN. |
| | |
| | 6) A100: PROVIDE VENTING DETAILS FOR THE DUST COLLECTOR |
| | AND SHAVING HOUSE. |
| | |
| | 7) REFER TO SECTION 301.15 AND PROVIDE WIND LOAD |
| | ENGINEERING FOR INSTALLATION OF THE DUCT WORK AND DUCT |
| | WORK SUPPORTS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |