| 2016-07-26 15:00:07 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | JOB NAME: JULIEN PORCH ENCLOSURE |
| | JOB ADDRESS: 1042 22ND STREET |
| | DESCRIPTION: LEGALIZATION OF UNPERMITTED ENCLOSURE |
| | MAST. PERMIT: 16070895 |
| | REVISION: |
| | |
| | ENCLOSING THE PORCH CONVERTS IT TO HABITABLE SPACE AND |
| | NO LONGER A PORCH, THEREFORE OUTLET AND LIGHTING PER |
| | CODE ARE REQUIRED. |
| | 1. NEC 210.52(A) STATES THAT THERE CAN BE NO MORE THAN |
| | 6 LINEAR FEET ALONG THE WALL BETWEEN OUTLETS. |
| | 2. NEC 210.52(E) REQUIRES THAT THERE ALSO BE AN OUTLET |
| | ON THE EXTERIOR AT THE FRONT OF THE HOME. |
| | 3. NEC 210.8 REQUIRES THAT THE EXTERIOR OUTLET BE GFCI |
| | PROTECTED. |
| | 4. NEC 210.12 REQUIRES THAT THESE CIRCUITS HAVE |
| | ARC-FAULT PROTECTION. |
| | 5. NEC 406.12 REQUIRES THAT RECEPTACLES IN A DWELLING |
| | BE TAMPER-RESISTANT. |
| | 6. THE PLANS SHOW COMPLIANCE WITH THE LIGHTING |
| | REQUIREMENTS OF NEC 210.70, BUT IN THE INTEREST OF |
| | ENERGY CONSERVATION, LIFE SAFETY AND CONSUMER |
| | CONVENIENCE, LET ME SUGGEST THAT THE LIGHTING IN THE |
| | ROOM BE CONTROLLED WITH A 3 WAY SWITCH. |
| | 7. PER FBC-R314.3 YOU SHALL COME INTO COMPLIANCE WITH |
| | THE SMOKE DETECTOR REQUIREMENTS, AND IF THE UNIT HAS |
| | FOSSIL FUEL BURNING APPLIANCES OR AN ATTACHED GARAGE, |
| | YOU SHALL COMPLY WITH FBC-R315, CARBON MONOXIDE |
| | DETECTION. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |
| 2016-07-25 09:05:30 | SEE PERMIT HISTORY, THERE APPEARS TO BE SIMILAR |
| | INCOMPLETE APPLIATIONS AND A REVOKED ONE AS WELL WITH |
| | POSSIBLE INCOMPLETE UNPERMITTED WORK. |