| Plan Review Notes For Permit 16070893 |
| Permit Number |
16070893 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-27 16:59:23 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1) IF THE KITCHEN IS BEING REMODELED AN ELECTRICAL SUB | | | PERMIT WILL BE REQUIRED. THE PLANS SHALL INCLUDE FBC-R | | | SECTIONS E3901.4 KITCHEN COUNTERTOP SPACE REQUIREMENTS | | | & E3703.2 SMALL APPLIANCE KITCHEN CIRCUITS. | | | | | | 2) SHOW LOCATIONS OF OUTLETS ON THE FLOOR PLAN INCLUDE | | | GFCI PROTECTION FOR , FBC-R SECTIONS E3902.6 KITCHENS & | | | E3902.7 SINK RECEPTACLES. | | | | | | 3) THE ISLAND SHALL HAVE A RECEPTACLE WITHIN 12'' OF | | | THE EDGE OF THE COUNTERTOP PER FBC-R E3901.4.2 ISLAND | | | COUNTER SPACES. | | | | | | 4) IS THE KITCHEN LIGHTING BEING MODIFIED PLEASE | | | CLARIFY ? FBC-E R404.1 A MINIMUM OF 75 PERCENT OF THE | | | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF | | | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | | CONTAIN ONLY HIGH EFFICACY LAMPS. |
|