| Plan Review Notes For Permit 16070890 |
| Permit Number |
16070890 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-10-31 11:26:38 | 2ND REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | 1] SINCE HABIATBLE SQUARE FOOTAGE IS BEING ADDED TO THE | | | DWELLING PLEASE PROVIDE EXISTING ELECTRIC SERVICE RISER | | | WITH WIRE SIZES, CONDUIT DETAIL AND GROUNDING DETAIL, | | | COMPLETE LOAD CALCULATIONS INCLUDING NEW ADDED LIVING | | | SPACE, AND PANEL SCHEDULES REFLECTING EXISTING | | | CIRCUITS. THIS INFORMATION IS NEEDED IN ORDER TO VERIFY | | | CAPACITY REQUIREMENTS FBC- 107.3.5.3. | | | | | | 2] ADD ELECTRICAL GENERAL NOTES FOR TAMPER-RESISTANT | | | RECEPTACLES AND ARC-FAULT PROTECTION PER FBC-R SECTIONS | | | E4002.14 & E3902.13. | | | | | | |
|