Plan Review Notes
Plan Review Notes For Permit 16070890
Permit Number 16070890
Review Stop B
Sequence Number 2
Notes
Date Text
2016-10-26 17:28:53PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE BUILDING CODE INFORMATION ON SHEET 1 INCORRECTLY
 REFERENCES THE 2016 EDITION OF THE FLORIDA BUILDING
 CODE WHICH DOES NOT EXIST. THE 2014 FLORIDA BUILDING
 CODE APPLIES TO THIS PROJECT. PLEASE REVISE.
  
 2) FBC-R 301.1 BUILDINGS AND STRUCTURES, AND ALL PARTS
 THEREOF, SHALL BE CONSTRUCTED TO SAFELY SUPPORT ALL
 LOADS, INCLUDING DEAD LOADS, LIVE LOADS, ROOF LOADS,
 FLOOD LOADS, AND WIND LOADS AS PRESCRIBED BY THIS CODE.
 THE CONSTRUCTION OF BUILDINGS AND STRUCTURES IN
 ACCORDANCE WITH THE PROVISIONS OF THIS CODE SHALL
 RESULT IN A SYSTEM THAT PROVIDES A COMPLETE LOAD PATH
 THAT MEETS ALL REQUIREMENTS FOR THE TRANSFER OF ALL
 LOADS FROM THEIR POINT OF ORIGIN THROUGH THE
 LOAD-RESISTING ELEMENTS TO THE FOUNDATION. SHOW
 COMPLIANCE. PROVIDE AN EXTERIOR WALL SECTION SHOWING
 ALL CONNECTORS THAT COMPRISE THE CONTINUOUS LOAD PATH
 FROM ROOF TO FOUNDATION. FBC 107.2.1.3
  
 3) PROVIDE ELEVATIONS OF THE PROPOSED WORK. FBC
 107.2.1.3
  
 4) IDENTIFY THE WINDOW TYPES ON THE PLANS (FOR EXAMPLE:
 SINGLE HUNG, FIXED, CASEMENT, ETC.) FBC 107.2.1
  
 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE WINDOWS.
  
 6) SHOW COMPLIANCE WITH FBC - R301.2.1.2 PROTECTION OF
 OPENINGS.
 GLAZED OPENINGS IN BUILDINGS LOCATED IN WINDBORNE
 DEBRIS REGIONS SHALL BE PROTECTED FROM WINDBORNE
 DEBRIS. GLAZED OPENING PROTECTION FOR WINDBORNE DEBRIS
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST
 OF ASTM E 1996 AND ASTM E 1886 REFERENCED THEREIN, SSTD
 12, TAS 201, 202 AND 203 OR AAMA 506, AS APPLICABLE.
 THE APPLICABLE WIND ZONES FOR ESTABLISHING MISSILE
 TYPES IN ASTM E 1996 ARE SHOWN IN SECTION R301.2.1.2.1.
 GARAGE DOOR GLAZED OPENING PROTECTION FOR WINDBORNE
 DEBRIS SHALL MEET THE REQUIREMENTS OF AN APPROVED
 IMPACT-RESISTING STANDARD OR ANSI/DASMA 115.
  
 7) FBC - R 301.2.1.2 SUBMIT TWO COPIES OF AN
 INSTALLATION SCHEDULE AND KEY PLAN FOR THE STORM
 PANELS. SPECIFY THE OPENING SIZE, THE WIND PRESSURES,
 TYPE OF ANCHOR, ANCHOR SPACING, EDGE DISTANCE, PANEL
 LENGTH, PANEL SPAN, SEPARATION DISTANCE FROM PANEL TO
 GLASS AND THE APPLICABLE SECTION NUMBER FROM THE
 INSTALLATION DRAWINGS. I HAVE INCLUDED A LINK TO THE
 CONSTRUCTION SERVICES DEPARTMENT SITE THAT HAS MANY OF
 THE RELATED FORMS INCLUDING THE SCHEDULE FOR
 INSTALLATION OF OPENING PROTECTIVE DEVICES.
 HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/
  
 8) SHOW COMPLIANCE WITH 2014 FBC ENERGY CONSERVATION
 SECTIONS 101.5.1 & 103.1 BY SUBMITTING THE PROPER
 CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS
 402 OR 405.
  
 9) SPECIFY THE WALL AND CEILING INSULATION R-VALUES
 THAT CORRESPOND TO THE ENERGY FORMS ON THE PLANS. FBC
 107.2.1
  
 10) SHOW COMPLIANCE WITH FBC-R806.1 FOR REQUIRED ROOF
 VENTILATION.
  
 11) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  