| Plan Review Notes For Permit 16070884 |
| Permit Number |
16070884 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-01-03 08:18:21 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16070884 | | | 1/3/17 | | | | | | 1) AS PREVIOUSLY REQUESTED PROVIDE A SCOPE OF WORK ON | | | THE PLANS, AND MINIMUM VENTILATION CALCULATIONS. | | | | | | 2) THE AC PLAN MUST BEAR THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN- SECTION 107.2.1 WPB | | | AMENDMENTS TO THE FBC. | | | | | | 3) PROVIDE THE SUPPLY DUCT SIZES IN OFFICES #1, 4, 5 * | | | 6. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|