| 2016-08-08 14:14:26 | JOB PERMIT NUMBER: 16070884 |
| | JOB ADDRESS: 770 NORTHPOINT PARKWAY |
| | WEST PALM BEACH FLORIDA SUITE # 102 |
| | DATE: AUGUST 8, 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | 1) CLARIFY IF ELECTRICAL POLES FOR CUBICLES ARE |
| | EXISTING? IF NOT PROVIDE MANUFACTURE SPECS. FBC 107 |
| | MINIMUM PLAN REVIEW |
| | 2) IF HAND DRYER OUTLET IS CORD AND PLUG CONNECTED THE |
| | RECEPTACLE SHALL BE GFCI PROTECTED. NEC 210(B)(1) |
| | 3) ADD EMERGENCY LIGHTING TO CUBICLE AREA FBC-1006.2. |
| | ILLUMINATION FOR THE MEANS OF EGRESS SHALL NOT BE LESS |
| | THAN 1' CANDLE AT THE WALKING SURFACE. |
| | 4) NEC 700.12 (F) (4) ? EMERGENCY/EXIT LIGHTING SHALL |
| | BE FED BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR |
| | MORE LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY |
| | BE ON OWN CIRCUIT. |
| | 5) PROVIDE MANDATORY LIGHTING CONTROLS FOR CUBICLE AREA |
| | FBC-E SECTION C405.2 |
| | 5A) FBC-E SECTION C405.2.1.2 LIGHTING REDUCTION |
| | 5B) FBC-E SECTION C405.2.2.1 AUTOMATIC TIME SWITCH |
| | 5C) FBC-E SECTION C405.2.2.3 DAYLIGHT ZONE CONTROL |
| | 5D) FBC-E SECTION C405.3 TANDEM WIRING |
| | 6) NEC 410.36(B) SUSPENDED CEILING SHALL BE SECURELY |
| | ATTACHED TO THE BUILDING STRUCTURE AND LUMINAIRES |
| | FASTENED TO THE CEILING GRID FRAMING MEMBERS BY |
| | MECHANICAL MEANS, PLEASE VERIFY ANSI STANDARDS FOR FIRE |
| | RATED ASSEMBLY LOAD CAPACITY. PROVIDE A SUPPORTING |
| | DETAIL OR ADD A BLOCK NOTE. |
| | 7) FBC-E C405.7 AT THE LEAST 50% OF ALL 125-VOLT, 15- |
| | AND 20-AMPERE RECEPTACLES SHALL BE AUTOMATICALLY |
| | CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN |
| | OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE |
| | INSTALLED IN MODULAR PARTITIONS. |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. WHEN RESUBMITTING, FOR A |
| | QUICKER RETURN ON YOUR RE-SUBMITTAL, YOU ARE REQUIRED |
| | TO PROVIDE A RESPONSE LETTER (NARRATIVE) ADDRESSING |
| | EACH ITEM ALONG WITH THE STANDARD CITY RE-SUBMITTAL |
| | FORM. |
| | THE NARRATIVE SHOULD INCLUDE THE PLAN REVIEWER'S |
| | COMMENTS AND YOUR RESPONSE OR ACTION TO SAME. |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE |
| | SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. IF |
| | YOU HAVE FURTHER QUESTIONS, PLEASE DON'T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 561-805-6713 |
| | [email protected] |
| | |